Industrial Automation
ControlLogix 8 Point Counter Input
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Suitable for safety functions | No |
Digital inputs configurable | Yes |
Digital outputs configurable | No |
Voltage type of supply voltage | DC |
Type of electric connection | Screw connection |
Total backplane power | 1.47 W |
Thermal dissipation | 12.97 BTU/h |
Power dissipation | 3.8 W @ 60 °C (140 °F) |
Number of counters | 8 individually isolated |
Current draw | 275 mA @ 5.1V, 3 mA @ 24V |
Module keying | Electronic, software configurable |
ON-state current, max | 5 mA @ 30V DC |
Inputs | 8 individually isolated, standard input or counter-control functionality |
Isolation voltage | 250V (continuous), reinforced insulation type, inputs to backplane, 250V (continuous), basic insulation type, input to input |
Wire category | 1 - on signal ports |
Redundancy | No |
Short-circuit protection, outputs available | No |
Input voltage, nom | 24V DC |
Cyclic update time | 0.2 ms |
Change of state | Any transition |
Slot width | 1 |
RTB keying | User-defined mechanical |
Shock | Operating: 30 G, Non operating: 50 G |
Vibration | 2 G @ 10...500 Hz |
Surrounding air temperature, max | 60 °C |
North American temperature code | T4A |
Emissions | IEC 61000-6-4 |
ESD immunity | 6 kV contact discharges, 8 kV air discharges |
Relative humidity | 5...95% noncondensing |
Conducted RF immunity | 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz |
EFT/B immunity | ±4 kV at 5 kHz on signal ports |
Operating temperature | 0 to 60 °C |
Surge transient immunity | ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports |
Radiated RF immunity | 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz |
Nonoperating temperature | -40 °C |
Off-state current, max | 1.5 mA |
Counting frequency, max | 40 kHz |
Input impedance, max | 6 kΩ @ 30V DC |
Off-state voltage, max | 5V |
Voltage category | 12/24V DC sink/source |
Count range | 0...2,147,483,648 (31-bit counter) |
On-state current, min | 2 mA @ 10V DC |
Operating voltage | 10...30V DC |
Input delay time | OFF to ON: 14 μs nom/23 μs max + user-configurable filter time of 0...30,000 μs, ON to OFF: 14 μs nom/23 μs max + user-configurable filter time of 0...30,000 μs |
Reverse polarity protection | Reverse polarity protection: Yes |
IEC temperature code | T4 |
Enclosure type | None (open-style) |