Industrial Automation
ControlLogix AC Power Supplies


Type of voltage (input voltage) | AC |
Power output | 60 W |
Output voltage at DC | 5.1 V |
Input voltage, nom | 120/240V AC |
Inrush current, max | 20 A |
Input power, max | 81 W/91VA @ 50 ðC (122 ðF), 68 W/77VA @ 60 ðC (140 ðF) |
Current capacity | 8 A @ 50 ðC (122 ðF) @ 5.1V DC, 6 A @ 60 ðC (140 ðF) @ 5.1V DC |
Power output, max | 60 W @ 0...+50 ðC (+32...+122 ðF), 50 W @ 0...+60 ðC (+32...+140 ðF) |
Wire category | 1 - on power ports |
Hold-up time | 4 cycles @ 85...265V AC, 50/60 Hz, 60 W, 5 cycles @ 85...265V AC, 50/60 Hz, 50 W |
Wire size | 2.5 mmò (14 AWG) solid or stranded copper wire rated at 90 ðC (194 ðF), or greater, 1.2 mm (3/64 in.) insulation max |
Suitable for safety functions | No |
Type of output voltage | DC |
Input voltage at AC 50 Hz | 85 V |
Input voltage at AC 60 Hz | 85 V |
Redundancy capable | No |
Input frequency | 47 Hz |
Width | 78 mm |
Height | 140 mm |
Depth | 145 mm |
Enclosure type rating | None (open-style) |
Weight | 0.77 kg |
ISAGX | No |
Rockwell tire and rubber rated | No |
Conductor screw torque | 0.565 Nm |
Vibration | 2 G @ 10...500 Hz |
Relative humidity | 5...95% noncondensing |
Shock | Operating: 30 G |
Operating temperature | 0 ðC < Ta < +60 ðC (+32 ðF < Ta < +140 ðF) |
Voltage variation | IEC 61000-4-11: 30% dips for 1 period at 0ð and 180ð on AC supply ports, 60% dips for 5 and 50 periods on AC supply ports, ñ10% fluctuations for 15 min on AC supply ports, >95% interruptions for 250 periods on AC supply ports |