ControlLogix DC Power Supply


Type of voltage (input voltage) | DC |
Power output | 60 W |
Output voltage at DC | 5.1 V |
Input voltage at DC | 18 V |
Input voltage, nom | 24V DC |
Inrush current, max | 30 A |
Input power, max | 85 W @ 50 ðC (122 ðF), 70 W @ 60 ðC (140 ðF) |
Current capacity | 8 A @ 50 ðC (122 ðF) @ 5.1V DC, 6 A @ 60 ðC (140 ðF) @ 5.1V DC |
Power output, max | 60 W @ 0...50 ðC (32...122 ðF), 50 W @ 0...60 ðC (32...140 ðF) |
Wire category | 1 - on power ports |
Hold-up time | 30 ms @ 18...32V DC, 60 W, 40 ms @ 18...32V DC, 50 W |
Wire size | 2.5 mmò (14 AWG) solid or stranded copper wire rated at 90 ðC (194 ðF), or greater, 1.2 mm (3/64 in.) insulation max |
Suitable for safety functions | No |
Type of output voltage | DC |
Redundancy capable | No |
Width | 78 mm |
Height | 140 mm |
Depth | 145 mm |
Enclosure type rating | None (open-style) |
Weight | 0.77 kg |
ISAGX | No |
Rockwell tire and rubber rated | No |
Conductor screw torque | 0.565 Nm |
Vibration | 2 G @ 10...500 Hz |
Relative humidity | 5...95% noncondensing |
Shock | Operating: 30 G |
Operating temperature | 0 ðC < Ta < +60 ðC (+32 ðF < Ta < +140 ðF) |
Voltage variation | IEC 61000-4-29: 10 ms interruption on DC supply ports, 60% dips for 100 ms on DC supply ports, 100% dips for 50 ms on DC supply ports, ñ20% fluctuations for 15 min on DC supply ports, 5 s interruptions on DC supply ports |