ROCKWELL AUTOMATION 2080-RTD2
ROCKWELL AUTOMATION 2080-RTD2
ROCKWELL AUTOMATION 2080-RTD2
ROCKWELL AUTOMATIONAvailable

Micro800 2 Channel RTD Plug-In

2080 Micro800 System, 2-ch RTD Input (non-isolated)
Product Code: 2080-RTD2
Partner cod.: 2080-RTD2
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Tecnichal data
Number of analogue inputs2
Resolution of the analogue inputs14 Bit
Resolution of the analogue outputs14 Bit
Input, currentNo
Input, voltageNo
Input, resistorYes
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableNo
Output, currentNo
Output, voltageNo
Output signal configurableNo
Analogue inputs configurableNo
Analogue outputs configurableNo
Type of electric connectionScrew connection
Normal mode rejection ratio70 dB @ 50/60 Hz
Accuracy±1.0 °C @ 25 °C (77 °F)
Wire sizeSolid: 0.14 mm2 (26 AWG)...1.5 mm2 (16 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 (26 AWG)...1.0 mm2 (18 AWG) @ Rated @ 90 °C (194 °F) insulation maximum
Open circuit detection time8 to 1212
Suitable for safety functionsNo
SIL according to IEC 61508None
Common mode rejection ratio100 dB @ 50/60Hz
RTD types supported100 Ω Platinum 385, 200 Ω Platinum 385, 500 Ω Platinum 385, 1000 Ω Platinum 385, 100 Ω Platinum 392, 200 Ω Platinum 392, 500 Ω Platinum 392, 1000 Ω Platinum 392, 10 Ω Copper 427, 120 Ω Nickel 672, 604 Ω Nickel-Iron 518
Surrounding air temperature, max65 °C
North American temperature codeT4
Power consumption40 mA @ 3.3V
EmissionsCISPR 11 (IEC 61000-6-4): Class A
ESD immunityIEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges
EFT/B immunityIEC 61000-4-4: ±2 kV @ 5 kHz on shielded ports
Conducted RF immunityIEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Surge transient immunityIEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports
Operating temperature-20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock)
Radiated RF immunityIEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz,
Nonoperating temperature-40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
VibrationIEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz
ShockIEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount: 25 g, nonoperating, Panel Mount: 35 g nonoperating
Mounting torque0.2 Nm
Terminal screw torque0.22...0.25 Nm (1.95...2.21 lb-in) (using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Input impedance>5 MΩ
Explosion safety category for gasNone
Explosion safety category for dustNone