Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

ROCKWELL AUTOMATION 300-TOJ9400
ROCKWELL AUTOMATION 300-TOJ9400
ROCKWELL AUTOMATIONNot available

Contactor, NEMA, Size 00, 9 A, 24-60V 50-60 Hz/20-60V DC, 4 NO Poles, 0 NO 0 NC Auxiliary Contacts, Screw Terminals

Contactor,NEMA,Size 00,9 A, 24-60V 50-60 Hz/20-60V DC,4 NO Poles,1 NO 1 NC Auxiliary Contacts,Screw Terminals
Product Code: 300-TOJ9400
Partner cod.: 300-TOJ9400
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Tecnichal data
Number of normally open contacts as main contact4
Number of normally closed contacts as main contact0
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Vibration resistanceIEC 60068-2-6
Shock resistanceIEC 60068-2-27
Altitude, max2000 m of installation site
Switching frequency, max600 ops/hr, AC-1
WeightAC/DC (electronic): 0.43 kg (0.95 lbs.)
Protection classContactor main contact: IP2X
Voltage type for actuatingAC/DC
Rated control supply voltage at AC 50 Hz24 V
Rated control supply voltage at AC 60 Hz24 V
Rated control supply voltage at DC20 V
Type of electrical connection of main circuitScrew connection
Rated impulse voltage withstand (Uimp)6 kV
NEMA size00...8
Operating time, closing delay40 ms
Operating time, opening delay11 ms
Main current circuit resistance0.41 mΩ
Rated isolation voltage (Ui)690V per IEC
FunctionEnergy-saving contactor
Standard coil, pick-up50VA/50 W @ 24-60V AC, 20-60V DC
Standard coil, hold-in2.2VA/2 W @ 24-60V AC, 20-60V DC
General purpose current (enclosed)13.8 A @ 600V per UL/CSA
Power dissipation0.8 W per pole at Ie, AC-1, 400V
Short time withstand (Icw)3-pole: 80 A for 30 s (40 °C)
FLA20 A @ 600V, 3-phase per UL/CSA HVAC applications
Rated operational current and power (enclosed)9.5 A @ 125V DC, with 3-poles in series per UL/CSA
Rated current4-Pole: 25 A @ 690V, AC-1, Ie at 40 °C
LRA80 A @ 550-600V AC, 3-phase per UL/CSA HVAC applications
Electromagnetic compatibilityIEC 60947-1 - Environment A and B
Total power dissipation2.3 W at Ie, AC-3, 400V, AC/DC control (120-250V)
Operating limits, dropout(≤0.60) x Us @ DC control
Operating limits, pick-up(0.85...1.1) x Us @ 50/60 Hz
MCCB current ratingType 2 (per IEC 60947-4-1): 28 A @ 400V, 70 kA available fault current
DIN fuses (gG) current ratingType 2 (per IEC 60947-4-1): 6 A @ 690V, 60 kA available fault current
Rated voltage (Ue)24V, 48V, 110V, 220V, 440V DC
Rated operational current and power5.8 A @ 115V AC, 500000 electrical operations, 1-phase per UL/CSA elevator duty
Switching of lighting loadsTungsten lamps: 20 A @ 600V, 3-phase (break all lines) per UL/CSA
UL class RK5 fuses ratingType 1 Combination (per UL 60947 and CSA 22.2 No. 14): 30 A @ 600V, 5 kA available fault current
Rated operational current (Ie)9.5 A @ 500V, Star-Delta starting (50 Hz)
UL class J and CSA HRCI-J fuses ratingType 1 Combination (per UL 60947 and CSA 22.2 No. 14): 30 A @ 600V, 100 kA available fault current
UL inverse-time circuit breakerType 1 Combination (per UL 60947 and CSA 22.2 No. 14): 60 A @ 600V, 5 kA available fault current
Switching of power transformersApparent power: 8 kVA @ 415V, AC-6a, 50 Hz (n = 30)
Rated operational power (Pe)9 kW @ 240V, AC-1 active power load (50/60 Hz), ambient temperature 70 °C (158 °F)
Switching of DC loads4-poles in series: 6 A @ 440V (Shunt-wound motors starting, reverse current breaking, reversing, stepping DC-3 at 60 °C)
Optional accessoriesSide- or front-mount auxiliary contacts, Mechanical interlocks, Terminal lugs, Terminal shields, Connecting bars
FeaturesCompact size, Sizes 00...5: AC/DC electronic coil with optional PLC interface, Sizes 6...8: AC/DC with PLC interface, Integrated surge suppression, Panel or DIN Rail mountable, Finger safe, Complete range of accessories, Meets global standards, Consists o
ContactsSizes 0...3: 3 power poles with internal N.O. or N.C. auxiliary contact or 4 power poles., Sizes 1...3: 3 power poles with side mounted N.O. / N.C. auxiliary contact or 4 power poles, Sizes 4...8: 3 main poles with 2 auxiliary contacts (1 N.O. and 1 N.C.)
CoilElectronic
Climatic withstandCategory B according to IEC 60947-1, annex Q
Ambient temperatureStorage range: -55...80 °C (-67...176 °F)
Coil insulation classClass F per IEC 60947-4-1