SICK 1085345
SICKNot available

RLY3-EMSS100

Safety relays: ReLy
Product Code: 1085345
Partner cod.: 1085345
SICK


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Tecnichal data
Features
ApplicationsEvaluation unit
Compatible sensor typesSafety sensors with potential-free outputs
Safety-related parameters
Safety integrity levelSIL 3 (IEC 61508)
CategoryCategory 4 (ISO 13849-1)
Performance levelPL e (ISO 13849-1)
PFHD (mean probability of a dangerous failure per hour)1.0 x 10-9
TM (mission time)20 years (ISO 13849-1)
Stop category0 (IEC 60204-1)
Functions
Sensor monitoring

Discrepancy monitoring

Cross-circuit detection

Restart interlock
Reset

Automatic

Manual

External device monitoring (EDM)
Interfaces
Connection typeFront connector with spring terminals
Inputs

2 safety inputs

1 input for reset pushbutton or external device monitoring (EDM)

Outputs

2 enabling current paths (safe)

2 application diagnostic outputs (not safe)

3 test pulse outputs (not safe)

Display elementsLEDs
Configuration methodHard wired
Electrical data - Operating data
Voltage supplyPELV or SELV
Supply voltage VS24 V DC (16.8 V ... 30 V)
Residual ripple≤ 2.4 V
Power consumption≤ 2.5 W (DC)
Electrical data - Safety inputs
Number2
Input voltage
HIGH24 V DC (11 V ... 30 V)
LOW0 V DC (–3 V ... 5 V)
Input current4 mA ... 6 mA
Activation time tolerance between the two start buttons≤ 3 s
Electrical data - Reset pushbutton or external device monitoring (EDM) input
Number1
Input voltage
HIGH24 V DC (11 V ... 30 V)
LOW0 V DC (–3 V ... 5 V)
Input current4 mA ... 6 mA
Electrical data - Enabling current paths
Response time10 ms
Number2
Type of outputN/O contacts, positively guided
Contact materialSilver alloy, gold flashed
Switching voltage

10 V AC ... 230 V AC

10 V DC ... 230 V DC

Switching current10 mA ... 6 A
Total current12 A
Mechanical life1 x 107 switching cycles
Overvoltage categoryIII (EN 60664-1)
Rated impulse withstand voltage Uimp6 kV (EN 60664-1)
Electrical data - Application diagnostic outputs
Number2
Type of outputPush-pull semiconductor output, short-circuit protected
Output voltage
HIGH≥ Vs – 3 V
LOW≤ 3 V
Input current (NPN)≤ 15 mA
Output current (PNP)≤ 120 mA
Electrical data - Test pulse outputs
Number3
Type of outputPNP semiconductors, short-circuit protected
Output voltage≥ Vs – 3 V
Test pulse width2 ms
Test pulse interval40 ms
Mechanical data
Dimensions (W x H x D)18 mm x 124.6 mm x 85.5 mm
Weight130 g
Ambient data
Enclosure ratingIP20 (IEC 60529)
Ambient operating temperature–25 °C ... +55 °C
Storage temperature–25 °C ... +70 °C
Air humidity≤ 95 %, Non-condensing
Interference emissionAccording to IEC 61000-6-4
Interference resistance

According to IEC 61326-3-1

According to IEC 61000-6-2

According to IEC 60947-5-1

Classifications
eCl@ss 5.027371990
eCl@ss 5.1.427371990
eCl@ss 6.027371819
eCl@ss 6.227371819
eCl@ss 7.027371819
eCl@ss 8.027371819
eCl@ss 8.127371819
eCl@ss 9.027371819
eCl@ss 10.027371819
eCl@ss 11.027371819
eCl@ss 12.027371819
ETIM 5.0EC001449
ETIM 6.0EC001449
ETIM 7.0EC001449
ETIM 8.0EC001449
UNSPSC 16.090141113704
Technical Specs
Unit weight0.172 Kilograms
Net unit weight0.172 Kilograms
Unit volume365.848 Cubic Centimetres (cm³)
Measurements9.400*2.800*13.900
Country of originHungary
EAN4047084415746