SICK 1100211
SICKNot available

FTMG-ISD15AXX

Flow sensors: FTMg
Product Code: 1100211
Partner cod.: 1100211
SICK


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Tecnichal data
Features
Measurement principleCalorimetric (flow, temperature), piezoresistive (pressure)
MediumCompressed air (air quality ISO 8573-1:2010 [3:4:4]), Argon, nitrogen, carbon dioxide
Measured valuesMass, Mass flow rate, volume, Volumetric flow rate, Energy, Flow velocity, pressure, Temperature
Nominal width measuring tubeDN 15
Measuring range
Standard5.3 l/min ... 1,060.3 l/min 
0.5 m/s ... 100 m/s 
Enhanced1,060.3 l/min ... 1,590.4 l/min 
100 m/s ... 150 m/s 
Process temperature–20 °C ... +60 °C
Process pressure0 bar ... 16 bar
Communication interfaceIO-Link, IO-Link V1.1
Temperature measurement
Pressure measurement
Indication
128 x 128 pixels, adjustable rotary OLED display (90° steps) and 4 pushbuttons
Performance
Measurement accuracy
Standard± 3 % of the measured value + 0.3% of the measuring range limit value (extended measuring range) 
Enhanced± 8 % of the measured value + 1% of the measuring range limit value (extended measuring range) 
Repeatability± 1.5 % From measured value 
Response time< 0.3 s
Temperature measurement
Measurement accuracy (temperature)± 2 °C 
Repeatability (temperature)± 0.5 °C 
Pressure measurement
Measurement accuracy (pressure)± 1.5 % of measuring range end value 
Non-linearity (pressure)± 0.5 % from measuring range 
Repeatability (pressure)± 0.2 % from measuring range 
Electronics
Supply voltage17 V DC ... 30 V DC 
Power consumption< 4.5 W at 24 V DC without output load
Initialization time≤ 10 s
Protection classIII
Connection typeM12 x 1 round connector, 5-pin, A-coded
Output signal1x analog output 4 mA ... 20 mA + 1x digital/analog output (PNP, NPN, push-pull, 4 mA ... 20 mA / switchable), frequency pulse output + 1x digital output (PNP, NPN, push-pull, switchable), IO-Link V1.1 (COM3 / 230K4 baud)
Output load4 mA ... 20 mA, max. 500 ohm
Lower signal level3.5 mA ... 3.8 mA
Upper signal level20.5 mA ... 21.5 mA
Inaccuracy

QA Pin2: < 0.5% full-range (20 mA)

Q2 Pin5: < 0.5% full-range (20 mA)

Digital output≤ 100 mA
Inductive load≤ 1 H
Capacitive load≤ 100 nF (2.5 nF, IO-Link mode)
MTTF> 100 years
Mechanics
Process connectionG ½ (according to DIN ISO 228-1)
Wetted partsProbe: stainless steel 1.4305, PA6; seal: FKM (Viton®); measurement channel: aluminum
Housing materialPC+ABS, PA66+PA6I GF50, PC, TPE, stainless steel 1.4301
Enclosure ratingIP65/IP67 (according to IEC 60529) 
WeightApprox. 805 g
Ambient data
Ambient operating temperature–20 °C ... +60 °C 
Ambient temperature, storage–40 °C ... +85 °C
Classifications
ECLASS 5.027200403
ECLASS 5.1.427200403
ECLASS 6.027200403
ECLASS 6.227200403
ECLASS 7.027200403
ECLASS 8.027200403
ECLASS 8.127200403
ECLASS 9.027200403
ECLASS 10.027200403
ECLASS 11.027200403
ECLASS 12.027200403
ETIM 5.0EC002580
ETIM 6.0EC002580
ETIM 7.0EC002580
ETIM 8.0EC002580
UNSPSC 16.090141112501
Technical Specs
Unit weight0.902 Kilograms
Net unit weight0.902 Kilograms
Unit volume2162.16 Cubic Centimetres (cm³)
Measurements13.500*8.800*18.200
Country of originGermany
EAN4047084456299