Automazione Industriale
MSI-SR-CM32-01
Safety relay
Cod. Articolo: 50133012 ![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Cod. Fornitore: 50133012 ![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
LEUZE
Basic data | Series: MSI-SR-CM32 Application: Extension unit for base devices in safety applications |
Functions | Functions: Monitoring of proximity switches Restart: Automatic |
Characteristic parameters | SIL: 3, IEC 61508 SILCL: 3, IEC/EN 62061 Performance Level (PL): e, EN ISO 13849-1 MTTFd: 74 years, EN ISO 13849-1 PFHD: 3,5E-10 per hour Mission time: 20 years, EN ISO 13849-1 Category: 4, EN ISO 13849-1 B10d at DC13 (inductive load): 300,000 number of cycles, (5 A, 230 V), 700,000 (1 A, 230 V) B10d at AC15 (inductive load): 200,000 number of cycles, (5 A, 230 V), 380,000 (1 A, 230 V) |
Electrical data | Supply circuit Nominal voltage UN: 24 V DC Nominal frequency: 50 ... 60 Hz Operating voltage: 0.85 ... 1.1 x UN Rated power DC: 1.2 W Galvanic isolation between supply and control circuit: No Output circuit Number of outputs, safety-oriented, undelayed, contact-based: 3 Piece(s) Number of outputs, signaling function, undelayed, contact-based: 2 Piece(s) Release current paths: NO Signaling current paths: NC Contact material: Ag alloy, gold-plated Usage category AC-15 (NO contact): Ue 230V, Ie 3A Usage category DC-13 (NO contact): Ue 24V, Ie 2,5A Short circuit protection (NO contact): gG class safety fuse 6A, melting integral Nominal switching voltage, release current paths AC: 230 V Nominal switching voltage, signaling current paths AC: 230 V Max. thermal continuous current Ith, release current paths: 6 A Max. thermal continuous current Ith, signaling current paths: 2 A Max. total current I² of all current paths: 9 A² Mechanical life time: 100,000,000 switching cycles Control circuit Input current at the control inputs (safety circuit/reset circuit): 50 mA Max. peak current at the control inputs (safety circuit/reset circuit): 500 mA Max. cable resistance, per channel: ≤ (5 + (1.6 x UB / UN - 1) x 100) Ω Response time (manual start tA1): 40 ms Test pulse time permitted tTP: 1 ms Release time tR: 20 ms Recovery time tW: 40 ms |
Connection | Number of connections: 1 Piece(s) Connection 1 Function: Signal IN Signal OUT Voltage supply Type of connection: Terminal Type of terminal: Screw terminal No. of pins: 14 -pin Cable properties Connection cross sections: 1 x 0.2 to 2.5 mm², wire 1 x 0.25 to 2.5 mm², wire with wire-end sleeve 2 x 0.2 to 1.0 mm², wire 2 x 0.25 to 1.0 mm², wire with wire-end sleeve |
Mechanical data | Dimension (W x H x L): 22.5 mm x 96.5 mm x 114 mm Net weight: 210 g Housing color: Gray Type of fastening: Snap-on mounting |
Certifications | Certifications: TÜV Rheinland c UL US |