Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 0914183
PHOENIX CONTACTNon disponibile

TMC 1 F1 100 16,0A - Thermomagnetic device circuit breaker

Thermal-magnetic circuit breaker, 1-pos., fast blow, 1 N/O contact, with universal foot for mounting on NS 32 or NS 35
Cod. Articolo: 0914183
Cod. Fornitore: 0914183
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Product propertiesType: DIN rail module, one-piece
Product type: Thermomagnetic device circuit breakers
Product family: TMC
Number of positions: 1
Number of connections: 4
Number of rows: 2
No. of channels: 1
Insulation characteristics
Overvoltage category: II
Degree of pollution: 2
Electrical propertiesNo. of channels: 1
Fuse type: Automatic device
General
Rated voltage: 65 VDC
Rated current IN: 16 A
Rated surge voltage: 2.5 kV
Insulation resistance Riso: > 100 MΩ (500 V DC)
Auxiliary circuit: 240 VAC/1 A(Low-induction)
65 VAC/1 A(Low-induction)
Tripping method: TM (thermomagnetic)
Device resistance: 0.02 Ω
Rated short-circuit switching capacity Icn: 2500 A (32VDC)
Short-circuit switching capacity: 2000 A (UL 1077: 65 V DC)
Dielectric strength: 3000 VAC (Actuation area)
3000 VAC (Main to auxiliary circuit)
Switching cycles, max.: 10000 (At 1 x In, inductive)
Fuse: F1 (fast blow)
Indicator/remote signaling
Connection name: Auxiliary contact
Operating voltage: 250 VAC
65 VDC
Operating current: 16 A AC (Low-induction)
Connection dataMain contact
Screw thread: M3
Tightening torque: 0.6 ... 0.8 Nm
Stripping length: 12 mm
Internal cylindrical gage: A3
Conductor cross section rigid: 0.2 mm² ... 6 mm²
Cross section AWG: 24 ... 10 (converted acc. to IEC)
Conductor cross section flexible: 0.2 mm² ... 4 mm²
Conductor cross-section flexible (ferrule without plastic sleeve): 0.25 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve): 0.25 mm² ... 2.5 mm²
2 conductors with same cross section, solid: 0.2 mm² ... 0.75 mm²
2 conductors with same cross section, flexible: 0.2 mm² ... 0.75 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 2.5 mm²
Nominal current: 16 A
Auxiliary contact
Screw thread: M3
Tightening torque: 0.6 ... 0.8 Nm
Stripping length: 12 mm
Internal cylindrical gage: A1
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Cross section AWG: 24 ... 14 (converted acc. to IEC)
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross-section flexible (ferrule without plastic sleeve): 0.25 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve): 0.25 mm² ... 1.5 mm²
2 conductors with same cross section, solid: 0.2 m² ... 0.75 m²
2 conductors with same cross section, flexible: 0.2 m² ... 0.75 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve: 0.25 mm² ... 0.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 0.75 mm²
Main contact​
Connection method: Screw connection
Screw thread: M3
Tightening torque: 0.6 Nm ... 0.8 Nm
Stripping length: 12 mm
Conductor cross section flexible: 0.2 mm² ... 4 mm²
Conductor cross section rigid: 0.2 mm² ... 6 mm²
Conductor cross section AWG: 24 ... 10
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 4 mm²
Auxiliary contact​
Connection method: Screw connection
Screw thread: M3
Tightening torque: 0.6 Nm ... 0.8 Nm
Stripping length: 12 mm
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 2.5 mm²
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/b3c8d0ae5a91e74fbf8973a31f3e2610/-S204x204-FJPG
Width: 12.5 mm
Height: 82.5 mm
Depth: 96 mm
Material specificationsFlammability rating according to UL 94: V-2
Insulating material group: II
Insulating material: PA66
Mechanical propertiesMechanical data
Open side panel: No
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP30 (Actuation area)
IP20 (Connection area)
Ambient temperature (operation): -30°C ... 60°C
Humidity test: 240 h, 95 % RH, 40°C
Standards and regulationsStandards/specifications: EN60934
UL1077
MountingMounting type: DIN rail: 35 mm
Specifiche
ECLASSECLASS-11.0: 27141116
ECLASS-12.0: 27141116
ECLASS-13.0: 27140401
ETIMETIM 9.0: EC000899
UNSPSCUNSPSC 21.0: 39121400
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00005.pdf

Approvals_01871.pdf

Data_sheet_00052.pdf

Manufacturer_declaration_00671.pdf

Manufacturer_declaration_02062.pdf

Manufacturer_declaration_05733.pdf

Technical_drawing_05019.pdf

Various_00001.pdf