Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/418b78014174d342b4d3452c35b898da/-S204x204-FJPG Width: 45 mm Height: 130 mm Depth: 119 mm
|
Notes | General: Support by phone or on-site (fee is charged)
|
Material specifications | Housing material: Polycarbonate fiber reinforced
|
Mounting | Mounting type: DIN rail mounting
|
Interfaces | Ethernet (RJ45) Connection method: RJ45 Note on the connection method: Auto negotiation and autocrossing Transmission speed: 10/100/1000 Mbps Transmission physics: Copper Transmission length: 100 m (per segment) Signal LEDs: Data receive, link status No. of channels: 8 (RJ45 ports)
|
Output data | Digital Output name: Alarm output
|
Product properties | Type: Book type Product type: Switch Product family: Managed Switch 2000 MTTF: 381.77 Years (SN29500 standard, temperature25°C, operating cycle21%) 165.29 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 20.35 Years (SN29500 standard, temperature70°C, operating cycle100%) Special properties: Extended temperature range PROFINET mode preset, PROFINET status LEDs Signal delay: ⥠1.9 µs (Store-and-Forward mode, 10/100/1000Mbps, depending on the frame size) Insulation characteristics Protection class: III (VDE0106) Degree of pollution: 2 Switch functions Diagnostic functions: RMON History LLDP (Link Layer Discovery Protocol) SNMP-Traps N:1-Portmirroring ACD (Address Conflict Detection) SysLog CRC-Surveillance Basic functions: Store-and-forward switch, complies with IEEE802.3 Signal contact control voltage: typ. 24 VDC PROFINET conformance class: Conformance-Class B PROFINET device function: PROFINET device Fast Startup Filter functions: Quality of Service (8 priority classes) Class of Service DiffServ/DSCP Port-Priorisierung VLAN (up to 32 VLANs) IGMP Snooping/Querier (v1/v2) Auto-Query-Port Extended Multicast Filtering IP parameterization: DHCP-Client DHCP Option 82 (Relay Agent) DHCP server (pool-based, port-based) BootP DCP (Discovery and Configuration Protocol) MAC address table: 8k Management: Web-based management (HTTP/HTTPS) Role-based user management (LDAP, RADIUS) SNMPv1/v2/v3 Command Line Interface (Telnet, SSH) Redundancy: MRP (Media Redundancy Protocol) RSTP (Rapid Spanning Tree Protocol) FRD (Fast Ring Detection) Large Tree Support LACP (Link Aggregation Control Protocol) PROFINET S2 system redundancy Status and diagnostic indicators: LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (link/activity and speed), PROFINET status LEDs (BF, SF) Additional functions: Jumbo frames (max. 9,600bytes) Transmission of MMSandGOOSE (IEC 61850-8-1) Transmission of Modbus/TCP Time synchronization: SNTP (Simple Network Time Protocol) Security functions Port security: MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass Basic functions: Store-and-forward switch, complies with IEEE802.3
|
Electrical properties | Local diagnostics: US1/2 Supply voltage US1, US2 Green LED FAIL Div. LED red LINK Link status Green LED BF Bus errors LED red SF Group error LED red Maximum power dissipation for nominal condition: 7.8 W (US = Min, Tamb = Max, DOI = Max) Test voltage: 500 VDC Test section: for one minute 500 VDC Transmission medium: Copper Supply Supply voltage (DC): 24 VDC (redundant) Supply voltage range: 12 VDC ... 57 VDC Power supply connection: via COMBICON, max. conductor cross section 1.5 mm² Residual ripple: 3.6 VPP (within the permitted voltage range) Max. current consumption: 1.4 A (US = Min, Tamb = Max, DOI = Max) Typical current consumption: 280 mA (at US = 24VDC and 25°C ambient temperature) Current consumption: 280 mA Function Signal contact control voltage: typ. 24 VDC
|
Connection data | Connection method: Push-in spring connection Note on the connection method: Use only copper connecting cables providing the permitted temperature range (-40°C ... 75°C). Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 9 mm
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) Shock (operation): 30g (EN60068-2-27) Vibration (operation): in acc. with IEC 60068-2-6: 5g, 150 Hz Air pressure (operation): 80 kPa ... 110 kPa up to 2000m above mean sea level (Without derating) Air pressure (storage/transport): 79 kPa ... 108 kPa up to 2000m above mean sea level (Without derating)
|
Standards and regulations | Free from substances that could impair the application of coating: Yes
|
Approvals | Shipbuilding approval: Tested in accordance with IEC 60945 and IACSE10 ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: DEMKO 16 ATEX 1709X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx ULD16.0018 X UL, USA/Canada Identification: cULus UL Ex, USA / Canada Identification: Class I, Division 2, Groups A, B, C, and D, T4 Class I, Zone 2, AEx ec IIC T4 Ex ec IIC T4 Gc X Certificate: E366272 Note: UL60079-0 Ed. 6 / UL60079-7 Ed. 5, CSA22.2 No. 60079-0 Ed. 3 / CSAC22.2 No. 60079-7 Ed. 2 EAC Ex Identification: 2Ex e IIC T4 Gc X Certificate: RU C-DE.HB49.B.00118/21 The following continue to apply for EAC Ex: Identification: ÃÃø üþýÃðöõ øÃÿþûÃ÷þòðÃà ÿþÃ
þôÃÃøù ôþÿÃÃõýýÃù úþÃÿÃà Ãþ ÃÃõÿõýÃà ÷ðÃøÃà ýõ ýøöõ IP66. Ãð úþÃÿÃÃõ/ÃúðÃà ÃÿÃðòûõýøà ôþûöýð ñÃÃà Ãð÷üõÃõýð ÿÃõôÃÿÃõöôðÃÃðÃà ýðôÿøÃÃ, ÷ðÿÃõÃðÃÃðà þÃúÃÃòðÃà úþÃÿÃà øûø Ãúðà òþ ò÷ÃÃòþþÿðÃýþù ÷þýõ. ÃúÃÿûÃðÃðÃøà ÃÃÃÃþùÃÃòð ôþÿÃÃúðõÃÃà ÃþûÃúþ ÿÃø ÃÃûþòøø, ÃÃþ òÃõ þÿÃøÃõÃúøõ ÿþÃÃà ÷ðýÃÃà ÿþôúûÃÃõýýÃüø ÃÃÃÃþùÃÃòðüø øûø ÷ðúÃÃÃà ÿÃøûðóðõüÃüø ÷ðóûÃÃúðüø. CCC/China-Ex Identification: Ex ec IIC T4 Gc Certificate: 2022122310115629 Corrosive gas test Identification: ISA S71.04.2013 G3 Harsh Group A UKCAEx(UKEX) Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIMA22UKEX2702910X DNV GL data Temperature: B Humidity: B Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board
|
EMC data | Conformance with EMC directives: EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A EN 61000-6-2 EN 61000-4-5 (surge) Criterion B EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A EN 61000-6-2 EN 61000-6-4 (interference) ClassA EN 61000-6-2 EN 61000-6-4 (conducted interference) ClassA Noise immunity: EN 61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 61000-6-3
|
System properties | Functionality Basic functions: Store-and-forward switch, complies with IEEE802.3
|
Signaling | Status display: LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (link/activity and speed), PROFINET status LEDs (BF, SF)
|