PHOENIX CONTACT 1082024
PHOENIX CONTACT 1082024
PHOENIX CONTACTNon disponibile

PSR-MC45-3NO-1DO-24DC-SC - Safety relays

Safety relay for emergency stop, safety doors, and light grids up to SIL3, Cat.4, PLe, 1 or 2-channel operation, automatic or manual, monitored start, 3 enabling current paths, US=24VDC, plug-in screw terminal block
Cod. Articolo: 1082024
Cod. Fornitore: 1082024
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Descrizione
Download
Caratteristiche Tecniche
Product propertiesProduct type: Safety relays
Product family: PSRmini
Application: Emergency stop
Safety door
Transponder
Light grid
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3
Times
Typical response time: < 100 ms (automatic start)
< 100 ms (manual, monitored start)
Typ. starting time with Us: < 100 ms (when controlled via A1)
Typical release time: < 20 ms (on demand via the sensor circuit)
< 20 ms (when controlled via A1; applicative deactivation via A1/A2 is not permitted)
Restart time: < 1 s (Boot time)
Recovery time: 500 ms (following demand of the safety function)
Electrical propertiesMaximum power dissipation for nominal condition: 17.21 W (at UB=30V, IL²=72A²)
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage/insulation: Basic insulation 4kV between all current paths
Basic insulation 4kV between all current paths and housing
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 19.2 VDC ... 30 VDC
24 VDC -20%/+25% (provide external protection)
Rated control supply current IS: typ. 75 mA
Power consumption at US: typ. 1.8 W
Inrush current: typ. 2.2 A (Δt=300µs at Us)
Filter time: 1 ms (at A1 in the event of voltage dips at Us)
Protective circuit: Serial protection against polarity reversal
Suppressor diode 33V
Input dataDigital: Sensor circuit (S10, S12, S22)
Description of the input: safety-related sensor inputs
NPN (S10, S12),PNP(S22)
Number of inputs: 3
Input voltage range "0" signal: 0 V ... 5 V (S10, S12)
Input voltage range "1" signal: 19.2 V ... 30 V
Input current range "0" signal: 0 mA ... 2 mA (S10, S12)
Inrush current: < 5 mA (Typically with US at S10/S12, Δt=500µs)
> -5 mA (typically with US at S22/0V, Δt=500µs)
Filter time: max. 3 ms (Test pulse width of low test pulses)
> 1 s (Test pulse rate for low test pulse)
Where test pulse width<1ms: test pulse rate=5xtest pulse width
max. 1 ms (Test pulse width, high test pulse)
> 100 ms (Test pulse rate, high test pulse)
Unless test pulses are safety-related, they should be disabled.
Concurrence: ∞
Max. permissible overall conductor resistance: 150 Ω
Protective circuit: Suppressor diode 38.6V
Current consumption: < 4 mA (typically with US at S10/S12)
> -15 mA (typically with US at S22/0V)
Digital: Start circuit (S34, S35)
Description of the input: non-safety-related
NPN
Number of inputs: 2
Input voltage range "1" signal: 19.2 VDC ... 30 VDC
Inrush current: < 10 mA (typically with US, Δt=500µs)
Max. permissible overall conductor resistance: 150 Ω
Protective circuit: Suppressor diode 38.6V
Current consumption: 2.5 mA (Typically with US at S34)
1 mA (Typically with US at S35)
Output dataRelay: Enabling current paths (13/14, 23/24, 33/34)
Output description: 2 N/O contacts each in series, safety-related, floating
Number of outputs: 3
Contact switching type: 3 enabling current paths
Contact material: AgSnO2
Switching voltage: min. 5 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity: min. 50 mW
Inrush current: min. 10 mA AC/DC
max. 6 A
Switching capacity in accordance with IEC 60947-5-1: 5 A (24V (DC13))
5 A (250V (AC15))
Limiting continuous current: 6 A
Sq. Total current: 72 A2 (observe derating)
Switching frequency: 0.5 Hz
Mechanical service life: 10x 106 cycles
Output fuse: 6 A gL/gG
Signal: M1
Output description: PNP
non-safety-related
Number of outputs: 1
Voltage: approx. 23 VDC (Us-1V)
Current: max. 100 mA
Maximum inrush current: 1 A (Δt=5ms at Us)
Switching frequency: 0.5 Hz (ohmic)
Protective circuit: 33 V suppressor diode
Short-circuit protection: Yes
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque: 0.5 Nm ... 0.6 Nm
SignalingStatus display: 2 x green LEDs
Operating voltage display: 1 x green LED
DimensionsWidth: 22.5 mm
Height: 112.4 mm
Depth: 114.5 mm
Material specificationsHousing material: Polyamide
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Category: 4
Performance level (PL): e (5ADC13; 8760switching cycles/year or 5AAC15; 2190switching cycles/year)
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 3
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -40°C ... 60°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 85°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Shock: 15g for Δt=11ms (continuous shock: 10g for Δt=16ms)
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Identification: CE-compliant
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: EN60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: See derating curve
Mounting position: vertical or horizontal
Connection method: Screw connection
Specifiche
ECLASSECLASS-11.0: 27371819
ECLASS-12.0: 27371819
ECLASS-13.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Descrizione
Safety relay for emergency stop, safety doors, and light grids up to SILCL 3, Cat. 4, PL e, 1 or 2-channel operation, automatic or manual, monitored start, 3 enabling current paths, US = 24 V DC, plug-in screw terminal block
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00699.pdf

Approvals_00700.pdf

Approvals_01216.pdf

Approvals_01217.pdf

Data_sheet_00534.pdf

Manufacturer_declaration_01163.pdf

Manufacturer_declaration_01586.pdf

Manufacturer_declaration_05474.pdf

Manufacturer_declaration_06240.pdf

Package_slip_01977.pdf

Technical_drawing_07841.pdf