Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/badbb7940ec52349986d12d576240f6f/-S204x204-FJPG Width: 53.6 mm Height: 129.9 mm Depth: 77.14 mm Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
|
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China.
|
Material specifications | Color: traffic grey A RAL 7042
|
Interfaces | AxiolineFlocal bus No. of channels: 2 Connection method: Bus base module Transmission speed: 100 Mbps
|
System properties | Module Input address area: 0 Byte Output address area: 1 Byte Required parameter data: 12 Byte Required configuration data: 6 Byte
|
Output data | Digital Output name: Digital outputs Connection method: Push-in connection Connection technology: 2-conductor Number of outputs: 4 Output voltage: 24 V Maximum output current per channel: 48 mA Nominal output voltage: 24 V
|
Product properties | Type: block modular Product type: I/O component Product family: AxiolineF Scope of delivery: including bus base module and AxiolineF connectors
|
Electrical properties | Potentials: AxiolineF local bus supply (U Supply voltage: 5 VDC (via bus base module) Current draw: max. 60 mA typ. 40 mA Potentials: Supply for digital output modules (U Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 420 mA Electrical isolation/isolation of the voltage ranges Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: Field to functional earth: 500 VAC, 50 Hz, 1 min. Test voltage: Field to 5V or 24V supplies: 1500 VAC, 50 Hz, 1 min.
|
Connection data | Connection technology Connection name: AxiolineF connector Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm
|
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard) -40°C ... 70°C (Extended, see section âTested successfully: use under extreme ambient conditionsâ in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
|
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1)
|
Approvals | ATEX Identification: II 3(1) G Ex ec [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC Certificate: DEMKO 20 ATEX 2370X IECEx Identification: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC Certificate: IECEx UL 20.0044X UKCAEx(UKEX) Identification: II 3(1) G Ex ec [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC Certificate: UL22UKEX2508X Ex data UL, USA / Canada: Ind. Cont. Eq. (E238705) also Listed Ind. Cont. Eq. for haz. loc. E196811 Install in: Class I, Div. 2, Groups A, B, C, D T4 Intrinsically safe outputs for: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz loc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
|
Mounting | Mounting type: DIN rail mounting
|
Ex data | Safety data Max. output voltage Uo: 27.3 V Max. output current Io: 99 mA Max. output power Po: 676 mW Safety-related maximum voltage Um: 250 V A, B / IIC ((A, B, or IIC)): Max. external inductivity Lo / Max. external capacitance Co: / 0.088 µF 1.189 mH C/IIB, IIIC ((C, IIB, or IIIC)): Max. external inductivity Lo / Max. external capacitance Co: / 0.683 µF 12.9 mH D/IIA, E, F, G, Class III ((D, E, F, G, Class III, or IIA)): Max. external inductivity Lo / Max. external capacitance Co: / 2.28 µF 27.41 mH
|