Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1086901
PHOENIX CONTACTNon disponibile

AXL F EX IS DO4 SD 24-48 XC 1F - Digital module

AxiolineF, Digital output module, Digital outputs:4, 24 V, connection technology:2-conductor, Extremeconditions version, Intrinsically safe, Solenoid drive, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Cod. Articolo: 1086901
Cod. Fornitore: 1086901
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/badbb7940ec52349986d12d576240f6f/-S204x204-FJPG
Width: 53.6 mm
Height: 129.9 mm
Depth: 77.14 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Utilization restriction​
CCCex note: Use in potentially explosive areas is not permitted in China.
Material specificationsColor: traffic grey A RAL 7042
InterfacesAxiolineFlocal bus
No. of channels: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
Input address area: 0 Byte
Output address area: 1 Byte
Required parameter data: 12 Byte
Required configuration data: 6 Byte
Output dataDigital
Output name: Digital outputs
Connection method: Push-in connection
Connection technology: 2-conductor
Number of outputs: 4
Output voltage: 24 V
Maximum output current per channel: 48 mA
Nominal output voltage: 24 V
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Scope of delivery: including bus base module and AxiolineF connectors
Electrical propertiesPotentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 60 mA
typ. 40 mA
Potentials: Supply for digital output modules (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 420 mA
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: Field to functional earth: 500 VAC, 50 Hz, 1 min.
Test voltage: Field to 5V or 24V supplies: 1500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C (Standard)
-40°C ... 70°C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
ApprovalsATEX
Identification: II 3(1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
Certificate: DEMKO 20 ATEX 2370X
IECEx
Identification: Ex ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
Certificate: IECEx UL 20.0044X
UKCAEx(UKEX)
Identification: II 3(1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
Certificate: UL22UKEX2508X
Ex data
UL, USA / Canada: Ind. Cont. Eq. (E238705) also Listed
Ind. Cont. Eq. for haz. loc. E196811
Install in: Class I, Div. 2, Groups A, B, C, D T4
Intrinsically safe outputs for: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz loc
Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc
[AEx ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
MountingMounting type: DIN rail mounting
Ex dataSafety data
Max. output voltage Uo: 27.3 V
Max. output current Io: 99 mA
Max. output power Po: 676 mW
Safety-related maximum voltage Um: 250 V
A, B / IIC ((A, B, or IIC)): Max. external inductivity Lo / Max. external capacitance Co: / 0.088 µF
1.189 mH
C/IIB, IIIC ((C, IIB, or IIIC)): Max. external inductivity Lo / Max. external capacitance Co: / 0.683 µF
12.9 mH
D/IIA, E, F, G, Class III ((D, E, F, G, Class III, or IIA)): Max. external inductivity Lo / Max. external capacitance Co: / 2.28 µF
27.41 mH
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00042.pdf

Approvals_00043.pdf

Approvals_00172.pdf

Approvals_00173.pdf

Approvals_00875.pdf

Approvals_01910.pdf

Approvals_01911.pdf

Certification_00134.pdf

Certification_00135.pdf

Data_sheet_00540.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_00323.pdf

Manufacturer_declaration_06275.pdf

Package_slip_00165.pdf

Technical_drawing_08007.pdf

Various_00004.pdf