PHOENIX CONTACT 1088136
PHOENIX CONTACT 1088136
PHOENIX CONTACTDisponibile

AXL F BP SE6 - Module carrier

AxiolineF, Backplane, 6 slots for Axioline SmartElements, transmission speed in the local bus:100 Mbps, degree of protection: IP20
Cod. Articolo: 1088136
Cod. Fornitore: 1088136
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8edf7c18db5b524f8dfb3d5a845f1d7f/-S204x204-FJPG
Width: 55 mm
Height: 122.4 mm
Depth: 36.9 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
Complete module width: 55 mm
Complete module height: 124.6 mm
Complete module depth: 76.1 mm
Note: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
InterfacesAxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
SmartElement interface
Number of interfaces: 6
Connection method: Card edge connector
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: Wall mounting on horizontal or vertical DIN rail
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesPotentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC
Potentials: Communications power supply of the Smart Elements (U
Supply voltage: 3.3 VDC (using card edge connectors)
Potentials: I/O supply feed-in (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 16 A (provide external protection)
max. 12 A (Applications with UL approval, external fusing)
Current consumption: min. 1.5 mA (without connected SmartElements, with nominal voltage)
Power consumption: max. 480 W
max. 360 W (Applications with UL approval)
Protective circuit: Surge protection; Suppressor diode
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: I/O supply feed-in (UP)
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.5 mm² ... 2.5 mm²
Conductor cross section flexible: 0.5 mm² ... 2.5 mm²
Conductor cross section AWG: 20 ... 14
Stripping length: 8 mm
I/O supply feed-in (U
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.5 mm² ... 2.5 mm²
Conductor cross section, flexible: 0.5 mm² ... 2.5 mm²
Conductor cross section AWG: 20 ... 14
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
MountingMounting type: DIN rail mounting
Mounting position: Wall mounting on horizontal or vertical DIN rail
Specifiche
ECLASSECLASS-11.0: 27242610
ECLASS-12.0: 27242610
ECLASS-13.0: 27242610
ETIMETIM 9.0: EC001600
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01758.pdf

Approvals_01798.pdf

Approvals_01799.pdf

Data_sheet_00563.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_01286.pdf

Manufacturer_declaration_02465.pdf

Manufacturer_declaration_06303.pdf

Package_slip_00708.pdf

Technical_drawing_08048.pdf