Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1104888
PHOENIX CONTACTDisponibile

PSR-M-EF2-SDI16-SC - Extension module

Safe extension module with 16safe inputs, TBUS interface, up to SIL3, Cat.4/PLe, plug-in screw terminal block, TBUS connector included
Cod. Articolo: 1104888
Cod. Fornitore: 1104888
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Safety device
Application: Emergency stop
Light grid
Safety door
Insulation characteristics
Protection class: III
Times
Response time: see user manual
Restart time: min. 5 s (Boot time)
max. 10 s (Boot time)
Electrical propertiesMaximum power dissipation for nominal condition: 4.28 W (with max. permissible load)
Nominal operating mode: 100% operating factor
Interfaces: DIN rail TBUS for connection to the master module, supplied as standard
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage/insulation: Basic insulation 4kV between 24V power supply and I/Os to the housing
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 19.2 VDC ... 28.8 VDC
24 VDC -20%/+20% (external fuse, typically 4A)
Rated control supply current IS: typ. 40 mA
Power consumption at US: typ. 0.96 W
Inrush current: < 2.3 A (Δt=1ms at Us)
Filter time: typ. 5 ms (at A1 in the event of voltage dips at Us)
Protective circuit: Serial protection against polarity reversal
Input dataDigital: IN1...IN16
Description of the input: Safety-related digital inputs
IEC 61131-2 Type2
Number of inputs: 16
Input voltage range "0" signal: 0 VDC ... 5 VDC
Input voltage range "1" signal: 11 VDC ... 28.8 VDC
Input current range "0" signal: < 1 mA
Filter time: min. 3 ms ±2ms (adjustable)
max. 250 ms ±2ms (adjustable)
Test pulse rate ≥2xset filter time, min. Test pulse rate=10ms
Cable length: max. 100 m (per input)
Max. permissible overall conductor resistance: max. 1.2 kΩ (Input and reset circuit at US)
Current consumption: typ. 7.5 mA (typically with US)
max. 9.5 mA (at a control voltage of 28.8VDC)
Output dataClock: T1, T2, T3, T4
Output description: PNP, IEC 61131-2 Typ 0,1
Number of outputs: 4
Voltage: 24 VDC (via A1)
Output voltage when switched off: max. 0.1 V
Maximum inrush current: 1.1 A (Δt=3sat Us)
Limiting continuous current: 100 mA (per channel)
400 mA (Total current of all outputs)
Leakage current: max. 100 µA
Test pulses: ≤ 200 µs (Test pulse duration)
Test pulse rate=8xtCycle [ms]
Short-circuit protection: Yes (self-limitation at 1.1A)
Cable length: max. 100 m (per output)
Max. capacitive load: max. 470 nF
Max. inductive load: max. 2.4 mH
Discharging circuit: Yes, internal
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque: 0.5 Nm ... 0.6 Nm
SignalingStatus display: 1 x LED (green), 2 x LED (orange)
16 x LED (yellow)
Operating voltage display: 1 x green LED
Error indication: 2xLED (red)
DimensionsWidth: 22.61 mm
Height: 112.58 mm
Depth: 113.6 mm
Material specificationsHousing material: Polyamide PA non-reinforced
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Performance level (PL): e (2-channel wiring)
d (1-channel wiring)
Safety data: IEC 61508 - High-demand for 2-channel wiring
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - High-demand for 1-channel wiring
Safety Integrity Level (SIL): 2
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3 (2-channel wiring)
2 (1-channel wiring)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -10°C ... 55°C (observe derating)
Ambient temperature (storage/transport): -20°C ... 85°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 95 % (non-condensing)
Max. permissible relative humidity (operation): 95 % (non-condensing)
Shock: 10g for Δt=16ms (continuous shock, 1000 shocks in each space direction)
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Identification: CE-compliant
MountingMounting type: DIN rail mounting
Assembly instructions: Observe derating
Mounting position: vertical or horizontal
Connection method: Screw connection
Specifiche
ECLASSECLASS-11.0: 27371819
ECLASS-13.0: 27371819
ECLASS-12.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00901.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Certification_00224.pdf

Certification_00318.pdf

Data_sheet_00639.pdf

Manual_00057.pdf

Manual_00058.pdf

Manufacturer_declaration_01345.pdf

Manufacturer_declaration_02275.pdf

Manufacturer_declaration_05475.pdf