Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1104986
PHOENIX CONTACT 1104986
PHOENIX CONTACTNon disponibile

PSR-M-EF7-SAI4-PI - Extension module

Safe extension module with 4safe analog inputs, 0V...10V; 0mA or 4mA...20mA; TBUS interface, up to Cat.4/PLe, SIL3, plug-in Push-in terminal block, TBUS connector included
Cod. Articolo: 1104986
Cod. Fornitore: 1104986
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Descrizione
Download
Caratteristiche Tecniche
Product propertiesProduct type: Safety device
Application: Analog IN
Insulation characteristics
Protection class: III
Times
Response time: see user manual
Restart time: min. 5 s (Boot time)
max. 10 s (Boot time)
Electrical propertiesMaximum power dissipation for nominal condition: 2.76 W (with max. permissible load)
Nominal operating mode: 100% operating factor
Interfaces: DIN rail TBUS for connection to the master module, supplied as standard
Air clearances and creepage distances
Rated insulation voltage: 250 VAC
Rated surge voltage/insulation: Basic insulation 4 kV between all current paths and housing
Electrical isolation, 0.5kV functional insulation between logic and analog inputs and between the analog inputs
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 19.2 VDC ... 28.8 VDC
24 VDC -20%/+20% (external fuse, typically 6A)
Rated control supply current IS: typ. 82 mA (without sensor supply)
typ. 212 mA (with sensor supply)
Power consumption at US: typ. 1.96 W (without sensor supply)
typ. 5.08 W (with sensor supply)
Inrush current: max. 14 A (Δt=1ms at Us)
Filter time: typ. 5 ms (in the event of voltage dips at Us)
Protective circuit: Serial protection against polarity reversal
Input dataGeneral
Protective circuit: Overload protection of the current inputs; Suppressor diode
Analog
Input name: INS1, INS2, INS3, INS4
Description of the input: Safety-oriented analog inputs, configurable as current or voltage inputs, galvanically isolated
Number of inputs: 4
Connection technology: 2-conductor, 3-conductor or 4-conductor (2-conductor sensor signal + 2-conductor sensor supply)
Note regarding the connection technology: shielded
Scanning rate: 2.5/5/10/16.6/20/50/60/100/200/400/800/1000/2000/4000Hz
Current input signal: 0 mA ... 25 mA (Measuring range)
0 mA ... 20 mA (Configurable measuring range with diagnostics range 20.1mA...23mA)
4 mA ... 20 mA (Configurable measuring range with diagnostics range 20.1mA...23mA (upper limit), 2.5mA...3.8mA (lower limit))
Voltage input signal: 0 V ... 12 V (Measuring range)
0 V ... 10 V (Configurable measuring range with diagnostics range 10.05V...11.5V (upper limit), 0.1V (lower limit))
Max. permissible current: max. 35 mA (as current input)
Permissible voltage: max. 24 V (as current input)
max. 14 V (as voltage input)
Input resistance current input: 290 Ω ±25% (incl. internal protective circuit)
Input resistance of voltage input: 185 kΩ ±25%
A/D converter resolution: 16 bit
Resolution (current): 381 nA
Resolution (voltage): 152 µV
Precision: typ. ± 2 % (as current input, relative to the measuring range final value)
max. ± 2.5 % (as current input)
typ. ± 1 % (as voltage input, relative to the measuring range final value)
max. ± 1.5 % (as voltage input)
Temperature coefficients: typ. ± 0.07 %/K
max. ± 0.07 %/K
Limit frequency (3 dB): 160 Hz (RC low pass, 1storder, as current input)
4 Hz (RC low pass, as voltage input)
Frequency: 12 Hz (max. recommended sensor signal frequency, as current input)
2 Hz (max. recommended sensor signal frequency, as voltage input)
Permissible cable length: max. 100 m (per input)
Protective circuit: Overload protection of the current inputs
Overload protection of the voltage inputs
Output dataSensor supply: OUTS1/0V...OUTS4/0V
Description: Sensor supply voltage per analog input
Supply voltage: 24 VDC ±3%
Current: max. 30 mA (Sensor current recording per channel)
Short-circuit-proof: yes
Protective circuit: Overload protection Overload detection at 38mA
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 16
Stripping length: 10 mm
SignalingStatus display: 4x LED (yellow, red)
Operating voltage display: 1 x green LED
DimensionsWidth: 22.61 mm
Height: 107.74 mm
Depth: 113.6 mm
Material specificationsColor: yellow
Housing material: Polyamide PA non-reinforced
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Performance level (PL): e (2-channel wiring)
d (1-channel wiring)
Safety data: IEC 61508 - High-demand for 2-channel wiring
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - High-demand for 1-channel wiring
Safety Integrity Level (SIL): 2
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3 (2-channel wiring)
2 (1-channel wiring)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -10°C ... 55°C (observe derating)
Ambient temperature (storage/transport): -20°C ... 85°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 95 % (non-condensing)
Max. permissible relative humidity (operation): 95 % (non-condensing)
Shock: 10g for Δt=16ms (continuous shock, 1000 shocks in each space direction)
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Identification: CE-compliant
MountingMounting type: DIN rail mounting
Assembly instructions: Observe derating
Mounting position: vertical or horizontal
Connection method: Push-in connection
Specifiche
ECLASSECLASS-11.0: 27371819
ECLASS-13.0: 27371819
ECLASS-12.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Descrizione
Safe extension module with 4 safe analog inputs, 0 V ... 10 V; 0 mA or 4 mA ... 20 mA; TBUS interface, up to SILCL 3, Cat. 4/PL e, SIL 3, plug-in Push-in terminal block, TBUS connector included
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00901.pdf

Certification_00224.pdf

Certification_00318.pdf

Data_sheet_00645.pdf

Manual_00057.pdf

Manual_00058.pdf

Manufacturer_declaration_01348.pdf

Manufacturer_declaration_02189.pdf

Manufacturer_declaration_05475.pdf

Package_slip_01946.pdf

Technical_drawing_08537.pdf