Notes | General Note: LABS release â in accordance with test specification VWPV3.10.7:2005-0 When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules.
|
Product properties | Product type: Device circuit breakers Product family: CAPAROC Number of positions: 1 No. of channels: 2 Number of slots: 2 Insulation characteristics Protection class: III Pollution degree: 2
|
Electrical properties | No. of channels: 2 General Operating voltage: 10 VDC ... 30 VDC Rated voltage: 12 VDC 24 VDC Rated current IN: 4 ADC (per channel) 1/2/3/4ADC(Adjustable via rotary coding switches) 1/2/3/4ADC(can be set, in RC mode via power module with communication interface) Rated current (pre-adjusted): 1 A Rated surge voltage: 0.5 kV Tripping method: E (electronic) Feedback resistance: max. 35 VDC Switch-on delay: 50 ms (each channel preset by default) can be adapted with CAPAROC PMIOL and CAPAROC PMPN power modules Required backup fuse: Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. Short-circuit switching capacity: 300 A Dielectric strength: 35 VDC (Load circuit) Active current limitation: typ. 2.0x IN at IN ⤠3A typically 1.5x IN at IN = 4A Fuse: electronic Efficiency: > 99 % Closed circuit current I0: typ. 25 mA (no load at 24V) Power dissipation: typ. 0.6 W (no load at 24V) < 1.1 W (in nominal operation at 24V and 4A) Measuring tolerance I: ± 10 % (typ.) MTBF (IEC 61709, SN 29500): 11364927 h (at 25°C with 21% load) 5271554 h (at40°C with 34.25%load) 640731 h (at65°C with 100%load) Voltage drop: 0.06 V (at 4 A) Fail-safe element: 5 ADC (per output channel) Load circuit Shutdown time: 5 s (with overload 1.1â¦1.3xIN at IN ⥠4A) 5 s (for overload 1.1â¦1.7xIN at IN < 4A) ⤠400 ms (max. 450ms for high starting currents) typ. 20 ms (for short circuit > 1,5 x IN) Undervoltage switch-off: ⤠8.5 VDC (active) ⥠9.2 VDC (inactive) Overvoltage switch-off: ⥠32.5 VDC (active) ⤠30.5 VDC (inactive) Max. capacitive load: ⤠60000 µF (Depending on the current setting and the short-circuit current available)
|
Connection data | Fuse-protected output Connection method: Push-in connection Stripping length: 10 mm Conductor cross section flexible: 0.2 mm² ... 4 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 4 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 4 mm²
|
Signaling | Channel LED off: off (Channel switched off) Channel LED yellow: lit (Channel switched on, channel load>80%) two flashes (Check the installation, no communication to power module) Channel LED green: lit (Channel switched on) flashing (Channel switched on, coding switch position is not equal to set value) Channel LED red: lit (Channel switched off, over- or undervoltage active) ON temporarily (Channel switched off, 5s cool-down phase, overload or short-circuit release) flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) two flashes (Channel switched off, system total current limit exceeded) Channel LED red-yellow: flashing (Channel is overloaded and is switched off) Channel LED red-green: flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release)
|
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/b0f91290c277b94ba6f21ceffa4d4ef8/-S204x204-FJPG Width: 12.4 mm Height: 132.4 mm Depth: 111.3 mm (incl. DIN rail 7.5mm)
|
Material specifications | Material: PA 6 PC Flammability rating according to UL 94: V-0
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -30°C ... 65°C (The temperature range of the power module must be taken into consideration) Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ⤠4000 m (amsl) Humidity test: 96h, 95%RH, 40°C Shock (operation): 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) 25g (6ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) Vibration (operation): 5g (10 ... 150Hz / 10cycles / axis / X,Y,Z)
|
Approvals | UL approval Identification: UL/C-UL Listed UL 508 UL Recognized UL 2367 UL 121201 Class I, Division 2, Groups A, B, C, D, T4A NEC Class 2 according to UL 1310
|
Standards and regulations | Standards/specifications: EN61000-6-2 EN61000-6-3 EN60068-2-78 EN50178 EN60068-2-6 EN60068-2-27 Note: EMC â Immunity for industrial areas EMC â Emission for residential, business and commercial properties and small operations Environmental influences â Moisture and heat, constant Equipping power installations with electronic equipment Environmental influences â Vibrations (sinusoidal) Environmental influences â Shocks
|
Mounting | Mounting type: pluggable onto CAPAROC CR⦠current rail
|