Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1136245
PHOENIX CONTACT 1136245
PHOENIX CONTACTNon disponibile

PLC-RPT-230UC/21-21/SO46 - Relay Module

PLC-INTERFACE for protection against interference currents or interference voltages on the control side. Consisting of basic terminal block with Push-in connection and plug-in miniature relay with power contact, 2changeover contacts, 230VAC input voltage
Cod. Articolo: 1136245
Cod. Fornitore: 1136245
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
NotesGeneral: The PLC-ATP partition plate must be installed for voltages greater than 250V (L1, L2, L3) between identical terminal blocks on adjacent modules.
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
Product propertiesProduct type: Relay Module
Product family: PLC-INTERFACE
Application: Filter to prevent interference
Operating mode: 100% operating factor
Mechanical service life: approx. 3x 107 cycles
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 3
Electrical propertiesMaximum power dissipation for nominal condition: 2.3 W
Test voltage (Winding/contact): 4 kVrms (50Hz, 1min., winding/contact)
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage: 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)
Input dataCoil side
Nominal input voltage UN: 230 VAC
220 VDC
Input voltage range: 179.4 VAC ... 264.5 VAC (20°C)
171.6 VDC ... 253 VDC (20°C)
Mains frequency: 50/60 Hz
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 8.5 mA (50Hz)
10 mA (60Hz)
Typical response time: 7 ms
Typical release time: 10 ms
Typical release voltage: 60 VAC
Coil voltage: 110 VDC
Protective circuit: RC element
Bridge rectifier
Status display: Yellow LED
Output dataSwitching
Contact switching type: 2 changeover contacts
Type of switch contact: Single contact
Contact material: AgNi
Maximum switching voltage: 250 V AC/DC
Minimum switching voltage: 5 V (10mA)
Limiting continuous current: 6 A
Maximum inrush current: 15 A (300ms)
Min. switching current: 10 mA (5 V)
Interrupting rating (ohmic load) max.: 144 W (24VDC)
96 W (48VDC)
60 W (60VDC)
44 W (110VDC)
57 W (220VDC)
1500 VA (250VAC)
Switching capacity min.: 0.12 W
Switching capacity: 2 A (DC13, 24V)
0.2 A (DC13, 250V)
3 A (AC15, 24V)
3 A (AC15, 250V)
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG: 26 ... 14
DimensionsWidth: 14 mm
Height: 80 mm
Depth: 94 mm
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Relay): RT III (Relay)
Degree of protection (Installation location): IP54 (Installation location)
Ambient temperature (operation): -40°C ... 55°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
Shipbuilding approval
Certificate: TAE0000196
Corrosive gas test
Identification: ISA-S71.04. G3 Harsh Group
EN60068-2-60
DNV GL data
Temperature: D
Humidity: A
Vibration: B/C
EMC: B
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Electromagnetic compatibility: Conformance with EMC directive
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Specifiche
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Approvals_00240.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Approvals_01883.pdf

Manufacturer_declaration_01426.pdf

Manufacturer_declaration_02212.pdf

Manufacturer_declaration_03393.pdf

Manufacturer_declaration_03394.pdf

Manufacturer_declaration_03599.pdf

Manufacturer_declaration_06569.pdf

Package_slip_01742.pdf

Technical_drawing_09183.pdf