Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1362791
PHOENIX CONTACT 1362791
PHOENIX CONTACTNon disponibile

TRIO3-PS/3AC/24DC/20/8C/IOL - Power supply unit

Primary-switched power supply unit, TRIO POWER, Push-in connection, 8-channel electronic circuit breaker, IO-Link, DIN rail mounting, input: 3-phase, output: 24 V DC / 20 A, adjustable from 24 V DC ... 28 V DC
Cod. Articolo: 1362791
Cod. Fornitore: 1362791
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Caratteristiche Tecniche
Input dataAC operation
Supply system configuration: Star network (TN, TT, IT (PE))
Nominal input voltage range: 3x 400 V AC ... 500 V AC
Input voltage range: 3x 400 V AC ... 500 V AC -20 % ... +10 %
2x 400 V AC ... 500 V AC ±10 %
Typical national grid voltage: 3x 400 V AC
3x 480 V AC
Voltage type of supply voltage: AC
Inrush current: < 13 A (25 °C)
Inrush current integral (I2t): < 0.33 A2s
Frequency range (fN): 50 Hz ... 60 Hz ±10 %
Mains buffering time: typ. 28 ms (3x 400 V AC)
typ. 28 ms (3x 480 V AC)
Current consumption: 3x 0.77 A (3x 400 V AC)
3x 0.63 A (3x 500 V AC)
2x 1.37 A (2x 400 V AC)
2x 1.13 A (2x 500 V AC)
Protective circuit: Transient protection; Varistor
Power factor (cos phi): 0.93 (3x 480 V AC)
Device mains fuse: 3.15 A internal (device protection)
Recommended breaker for input protection: 3x 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: typ. 94.4 % (3x 400 V AC)
typ. 94.5 % (3x 480 V AC)
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN): 20 A
Dynamic Boost (IDyn.Boost): max. 30 A (5 s)
No. of channels: 8
Nominal current per channel: 1 A
2 A
3.8 A
4 A
6 A
8 A
10 A
Waiting time after switch off of a channel: 5 s
Switch-on delay of the channels: 100 ms
Short-circuit-proof: yes
No-load proof: yes
Derating: 60 °C ... 70 °C
Crest factor: typ. 1.51 (3x 400 V AC)
typ. 1.69 (3x 480 V AC)
Output power (PN): 480 W
Output power (PDyn. Boost): max. 720 W (5 s)
Connection in parallel: no
Connection in series: no
Max. capacitive load: 30 mF
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): ≤ 35 V DC
Residual ripple: typ. 15 mVPP (with nominal values)
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Rise time: ≤ 1 s (UOut = 10 % ... 90 %)
Minimum no-load power dissipation: < 3 W (3x 400 V AC)
Maximum no-load power dissipation: < 3.1 W (3x 480 V AC)
Minimum nominal load power dissipation: < 26.08 W (3x 400 V AC)
Power loss nominal load max.: < 27.35 W (3x 480 V AC)
Integrated fuse protection: yes
Signal relay 13/14
Position: 3.x
Position marking: 3.1 (13), 3.2 (14)
Switch contact (floating): OptoMOS
Switching voltage: max. 30 V DC (SELV)
Current carrying capacity: max. 100 mA
State condition: UOut > 21 V DC and IOut < 0.9 x IN (Contact closed)
UOut < 21 V DC or IOut > 0.9 x IN (averaging over 60 s) (Contact open)
Channel triggered or defective or OVP active
Connection dataInput
Position: 1.x
Connection technology
Position marking: 1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 ()
Conductor connection
Connection method: Push-in connection
rigid: 0.2 mm² ... 4 mm²
1.5 mm² (recommended)
flexible: 0.2 mm² ... 2.5 mm²
1.5 mm² (recommended)
flexible with ferrule without plastic sleeve: 0.25 mm² ... 2.5 mm²
1.5 mm² (recommended)
flexible with ferrule with plastic sleeve: 0.25 mm² ... 2.5 mm²
1.5 mm² (recommended)
rigid (AWG): 24 ... 12 (Cu)
16 (recommended)
Stripping length: 10 mm (Rigid/flexible/ferrule)
Output
Position: 2.x
Connection technologyâۉ€¹
Position marking: 2.1, 2.2, 2.3, 2.4, 2.5, 2.6, 2.7, 2.8 (+)
Conductor connectionâۉ€¹
Connection method: Push-in connection
rigid: 0.2 mm² ... 4 mm²
1.5 mm² (recommended)
flexible: 0.2 mm² ... 2.5 mm²
1.5 mm² (recommended)
flexible with ferrule without plastic sleeve: 0.25 mm² ... 2.5 mm² (Cu)
1.5 mm² (recommended)
flexible with ferrule with plastic sleeve: 0.25 mm² ... 2.5 mm²
1.5 mm² (recommended)
rigid (AWG): 24 ... 12 (Cu)
16 (recommended)
Stripping length: 10 mm (Rigid/flexible/ferrule)
Outputâۉ€¹
Position: 2.x
Connection technologyâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Position marking: 2.9, 2.10 (-)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Push-in connection
rigid: 0.2 mm² ... 10 mm²
4 mm² (recommended)
flexible: 0.2 mm² ... 6 mm²
4 mm² (recommended)
flexible with ferrule without plastic sleeve: 0.25 mm² ... 6 mm²
4 mm² (recommended)
flexible with ferrule with plastic sleeve: 0.25 mm² ... 6 mm²
4 mm² (recommended)
rigid (AWG): 24 ... 8 (Cu)
12 (recommended)
Stripping length: 12 mm (Rigid/flexible/ferrule)
Signal
Position: 3.x
Connection technologyâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Position marking: 3.1 (13), 3.2 (14)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Push-in connection
rigid: 0.2 mm² ... 1.5 mm²
0.5 mm² (recommended)
flexible: 0.2 mm² ... 1.5 mm²
0.5 mm² (recommended)
flexible with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (Cu)
0.5 mm² (recommended)
flexible with ferrule with plastic sleeve: 0.25 mm² ... 0.75 mm²
0.5 mm² (recommended)
rigid (AWG): 24 ... 16 (Cu)
20 (recommended)
Stripping length: 10 mm (Rigid/flexible/ferrule)
Communication
Position: 5.x
Connection technologyâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Position marking: 5.1 (L+), 5.2 (C/Q), 5.3 (L-)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Push-in connection
rigid: 0.2 mm² ... 1.5 mm²
0.5 mm² (recommended)
flexible: 0.2 mm² ... 1.5 mm²
0.5 mm² (recommended)
flexible with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (Cu)
0.5 mm² (recommended)
flexible with ferrule with plastic sleeve: 0.25 mm² ... 0.75 mm²
0.5 mm² (recommended)
rigid (AWG): 24 ... 16 (Cu)
20 (recommended)
Stripping length: 10 mm (Rigid/flexible/ferrule)
InterfacesIO-Link
Specification: V1.1
Interface: IO-Link
Number of interfaces: 1
Connection method: Push-in connection
Position: 5.x
Position marking: 5.1 (L+), 5.2 (C/Q), 5.3 (L-)
Transmission physics: 3-wire, standard industrial cable
Reverse polarity protection: yes
Transmission speed: 38.4 kbps (COM2)
Cycle time: 40 ms
Amount of process data: 6 Byte (Input data)
Device ID: 040116hex/262422dez
Vendor ID: 00B0hex / 176dez
SignalingLED signaling
Types of signaling: LED DC OK âۉ€œ signal state operation (UN = 24 V DC, IOut = IN)
Function: Visual operating state display
Color: red, yellow, green (multicolor LED)
LED off: Supply voltage input AC not present (Off)
LED on (green), DC OK: UOut > 21 V DC and IOut < 0.9 x IN (On (green), DC OK)
LED on (yellow), IOut > 90%: UOut > 21 V DC and IOut > 0.9 x IN (On (yellow), IOut > 90% )
LED on (flashing red) OVP: UOUT > OVP (Over voltage protection) (On (flashing red))
Electrical propertiesNumber of phases: 3.00
Insulation voltage input/output: 6 kV DC (type test)
3.1 kV DC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 1100000 h (25 °C)
> 600000 h (40 °C)
> 230000 h (60 °C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Data management status
Article revision: 00
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsItem dimensions
Width: 88 mm
Height: 135 mm
Depth: 132 mm
125 mm (Device depth (DIN rail mounting))
Installation dimensions
Installation distance right/left (active): 15 mm / 15 mm
Installation distance right/left (passive): 0 mm / 0 mm (≤ 40 °C)
MountingMounting type: DIN rail mounting
Assembly note: alignable: 0 mm horizontally, 30 mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: no
Material specificationsFlammability rating according to UL 94: V0 (Housing, terminal blocks)
Hood version: Polycarbonate
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Ambient temperature (start-up type tested): -40 °C
Maximum altitude: ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
Shock (operation): 18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation): 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6)
50 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsOvervoltage category
EN 61010-1: III (≤ 2000 m)
II (≤ 5000 m)
Overvoltage categoryâۉ€¹
EN 61010-2-201: III (≤ 2000 m)
II (≤ 5000 m)
Safety of power supply units up to 1100 V (insulation distances)
Standard designation: Safety of power supply units up to 1100 V (insulation distances)
Standards/specifications: DIN EN 61558-2-16
Electrical safety
Standard designation: Electrical safety
Standards/specifications: IEC 61010-2-201 (SELV)
Electronic equipment for use in power installations
Standard designation: Equipping high voltage installations with electronic equipment
Standards/specifications: EN 50178/VDE 0160 (PELV)
Safety for measurement, control, and laboratory equipment
Standard designation: Safety for equipment for measurement, control, and laboratory use
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Safe isolation
Standard designation: Safe isolation
Standards/specifications: IEC 61558-2-16
IEC 61010-2-201
Limitation of harmonic line currents
Standard designation: Limitation of harmonic line currents
Standards/specifications: EN 61000-3-2
Mains variation/undervoltage
Standard designation: Mains variation/undervoltage
Standards/specifications: SEMI F47
EN 61000-4-11
ApprovalsUL
Identification: UL/C-UL Listed UL 61010-1
ULâۉ€¹
Identification: UL/C-UL Listed UL 61010-2-201
UL/CSA
Identification: UL 1310 / CSA C22.2 No. 223 (NEC Class 2)
ULâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Identification: UL 2367 (Standard for Safety for Solid State Overcurrent Protectors)
ANSI/UL
Identification: PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS
(EN) ï‚· This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only.
(FR) ï‚· Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles.
(EN) ï‚· WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
(FR) ï‚· AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse.
(EN) ï‚· If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
(FR) ï‚· Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée.
(EN) ï‚· This equipement must be installed in a suitable, tool secured/key locked enclosure.
(FR) ï‚· Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil.
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunity: Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Conducted noise emission: EN 55016
EN 61000-6-3 (Class B)
Noise emission: EN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: EN 61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: asymmetrical 2 kV (Test Level 3)
Output: asymmetrical 2 kV (Test Level 3)
Signal: asymmetrical 1 kV (Test Level 3)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Input: symmetrical 1 kV (Test Level 3)
asymmetrical 2 kV (Test Level 3)
Output: symmetrical 0.5 kV (Test Level 2)
asymmetrical 1 kV (Test Level 2)
Signal: asymmetrical 1 kV (Test Level 2)
Comments: Criterion B
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN 61000-4-11
Voltage: 480 V AC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 periods
10 periods
1 period
Additional text: Class 3
Comments: Criterion A
Criterion B
Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Descrizione
TRIO3-PS/3AC/24DC/20/8C/IOL Alimentatore