PHOENIX CONTACT 2700975
PHOENIX CONTACTNon disponibile

ILC 171 ETH 2TX - Controller

The Inline controller offers the option of communicating via PROFINET and Modbus/TCP. Programming is carried out using PC Worx Express or PC Worx (IEC 61131-3).
Cod. Articolo: 2700975
Cod. Fornitore: 2700975
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
NotesUtilization restriction
CCCex note: Use in potentially explosive areas is not permitted in China.
Product propertiesType: modular
Product type: Controller
Product family: Inline-Controller
Display
Diagnostics display: No
System propertiesProcessor: Altera Nios II 64 MHz
Clock frequency: 64 MHz
Retentive data storage: 48 kByte (NVRAM)
IEC 61131 runtime system
Program memory: 512 kByte
Data storage system: 512 kByte
Number of control tasks: 8
INTERBUS-Master
Amount of process data: max. 4096 bit (INTERBUS)
Number of supported devices: max. 128
Number of local bus devices that can be connected: max. 63 (observe current consumption)
Number of devices with parameter channel: max. 24
Number of supported branch terminals with remote bus branch: max. 3
Modbus/TCP-Client
Amount of process data: max. 32768 bit (internal Modbus /TCP client)
Number of Modbus/TCP clients: max. 16 later than FW 4.42
PROFINET
Device function: PROFINET device
Specification: 2.2
Device ID: 007Ahex / 122dez
Vendor ID: 00B0hex / 176dez
Function
Diagnostics display: No
Controller redundancy: No
Safety function: No
Functionality
Programming languages supported: Instruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST)
System requirements
Engineering tool: PC Worx
PC Worx Express
Configuration tool: Config+ Version 1.01 or later
Diagnostics tool: DIAG+
Runtime system: eCLR
Application interface: OPC
Electrical propertiesTransmission medium: Copper
Real-time clock
Realtime clock: Yes
Description realtime clock: integrated (rechargeable battery buffered)
Potentials: 24 V supply U
Supply voltage: 24 VDC -15% / +20% (in accordance with EN61131-2)
Supply voltage range: 19.2 VDC ... 30 VDC
Current draw: 80 mA (without connected I/O terminal blocks)
Potentials: 7.5 V communications power U
Supply voltage: 7.5 VDC ±5%
Potentials: 24V analog supply U
Supply voltage: 24 VDC -15% / +20%
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Potentials: 24 V main supply U
Supply voltage: 24 VDC -15% / +20% (in accordance with EN61131-2)
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 8 ADC
6 mA (without sensors)
Potentials: 24 V segment supply U
Supply voltage: 24 VDC -15% / +20% (in accordance with EN61131-2)
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 8 ADC
10 mA (without actuators)
Input dataDigital
Input name: Digital inputs
Description of the input: EN 61131-2 type 1 NPN/PNP
Number of inputs: 8
Cable length: max. 30 m
Connection method: Inline potential distributor
Connection technology: 2-, 3-, 4-conductor
Input voltage range: -0.5 V ... 30 V
Input voltage range "0" signal: -0.5 V ... 5 V
Input voltage range "1" signal: 15 V ... 30 V
Nominal input current at UIN: typ. 7 mA
max. 15 mA
Input filter time: typ. 5 ms (Signal change 01)
typ. 5 ms ()
Output dataDigital
Output name: Digital outputs
Connection method: Spring-cage connection
Connection technology: 2-, 3-, 4-conductor
Number of outputs: 4
Maximum output current per channel: 500 mA
Maximum output current per module / terminal block: 2 A
Nominal load, lamp: 12 W
Nominal load, ohmic: 12 W
Behavior with inductive overload: Output can be destroyed
Connection dataInline connector
Connection method: Spring-cage connection
Conductor cross section, rigid: 0.08 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.08 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
InterfacesWeb server: yes
null
Bus system: RJ45
Number of interfaces: 2
Connection method: RJ45 jack
Transmission speed: 10/100 Mbps
No. of channels: 2
INTERBUS local bus (master)
Number of interfaces: 1
Connection method: Inline data jumper
Transmission speed: 500 kBaud / 2 MBaud (can be switched)
Parameterization/operation/diagnostics
Bus system: RS-232
Number of interfaces: 1
Connection method: 6-pos. MINI DIN socket (PS/2)
Transmission speed: max. 115.2 kbps
Transmission physics: Copper
No. of channels: 1
DimensionsWidth: 80 mm
Height: 119.8 mm
Depth: 71.5 mm
Material specificationsColor: green
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 55°C
Ambient temperature (storage/transport): -25°C ... 85°C
Permissible humidity (operation): 10 % ... 95 % (according to DINEN61131-2)
Permissible humidity (storage/transport): 10 % ... 95 % (according to DINEN61131-2)
Shock: 25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation): 5g
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37: Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity
EMC dataConformance with EMC directives: Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Fast transients (burst)EN61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1 kVCriterion B, all interfaces 2 kV
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Conducted interferenceEN61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN61000-6-4/IEC 61000-6-4 EN55011 ClassA
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
MountingMounting type: DIN rail mounting
Specifiche
ECLASSECLASS-11.0: 27242207
ECLASS-12.0: 27242207
ECLASS-13.0: 27242207
ETIMETIM 9.0: EC000236
UNSPSCUNSPSC 21.0: 32151700
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00108.pdf

Application_note_00109.pdf

Application_note_00082.pdf

Application_note_00189.pdf

Application_note_00132.pdf

Application_note_00051.pdf

Approvals_00156.pdf

Approvals_01165.pdf

Approvals_01166.pdf

Approvals_01202.pdf

Approvals_01479.pdf

Approvals_01497.pdf

Approvals_01554.pdf

Approvals_01895.pdf

Function_blocks_00002.pdf

Function_blocks_00003.pdf

Function_blocks_00004.pdf

Function_blocks_00005.pdf

Manual_00161.pdf

Manual_00146.pdf

Manual_00085.pdf

Manual_00162.pdf

Manufacturer_declaration_01038.pdf

Manufacturer_declaration_01503.pdf

Manufacturer_declaration_05551.pdf

Manufacturer_declaration_14514.pdf

Package_slip_01469.pdf

Package_slip_01470.pdf

Package_slip_02500.pdf

Package_slip_02501.pdf

Package_slip_02502.pdf

Product_information_00033.pdf

Product_information_00275.pdf

Technical_drawing_37659.pdf

Various_00088.pdf