PHOENIX CONTACT 2701228
PHOENIX CONTACTNon disponibile

AXL F DO16/3 XC 2F - Digital module

AxiolineF, Digital output module, Digital outputs:16, 24 VDC, 500 mA, connection technology:3-conductor, Extremeconditions version, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Cod. Articolo: 2701228
Cod. Fornitore: 2701228
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Descrizione
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f4dbc4c57447e643bed727029bb8cde0/-S204x204-FJPG
Width: 53.6 mm
Height: 129.9 mm
Depth: 54 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
InterfacesAxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
Input address area: 0 Byte
Output address area: 2 Byte
Required parameter data: 1 Byte
Required configuration data: 6 Byte
Output dataDigital
Output name: Digital outputs
Connection method: Push-in connection
Connection technology: 3-conductor
Number of outputs: 16
Protective circuit: Short-circuit protection, overload protection of the outputs; electronic
Output voltage: 24 V
Limitation of the voltage induced on circuit interruption: -25.8 V ... -15 V
Maximum output current per module: max. 8 A (provide external protection)
Nominal output voltage: 24 VDC
Load min.: 10 kΩ
Output voltage when switched off: max. 1 V
Output current when switched off: max. 300 µA
Nominal load, inductive: max. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lamp: max. 12 W (at nominal voltage)
Nominal load, ohmic: max. 12 W (48 Ω, with nominal voltage)
Switching frequency: max. 10000 per second (with at least 50mA load current)
max. 1 per second (with inductive load)
max. 16 per second (with nominal lamp load)
Reverse voltage resistance to short pulses: limited protection up to 0.5 A for 1 s
Behavior with overload: Shutdown with automatic restart
Behavior with inductive overload: Output can be destroyed
Signal delay: max. 100 µs (when switched on)
max. 100 µs (when switched off, with at least 50 mA load current)
Overcurrent shut-down: as of 0.7 A
Output current with ground connection interrupt when switched off: < 1 mA
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (no temperature derating)
Scope of delivery: including bus base module and AxiolineF connectors
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesMaximum power dissipation for nominal condition: 1.16 W
Potentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 120 mA (HW 00)
max. 60 mA (from HW01)
Power consumption: max. 600 mW (HW 00)
max. 300 mW (from HW01)
Potentials: Supply for digital output modules (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 8 A (provide external protection)
Power consumption: max. 240 W (of which 560mW with internal losses)
Protective circuit: Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5A fuse (only for commissioning)
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zone2 potentially explosive area)
-40°C ... 70°C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
ApprovalsATEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: UL 20 ATEX 2441X
UKEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: PxCIMA22UKEX2701949X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx ULD 20.0026X
UL, USA/Canada
Identification: cULus
Certificate: E238705
UL Ex, USA / Canada
Identification: Class I, Zone 2, AEx ec IIC T4
ClassI, Division2, Groups A, B, C, D, T4
Ex ec IIC T4 Gc X
Certificate: E366272
CCC/China-Ex
Identification: Ex ec IIC T4 Gc
Certificate: , 2021122309114456
MountingMounting type: DIN rail mounting
Mounting position: any (no temperature derating)
Specifiche
ECLASSECLASS-11.0: 27242604
ECLASS-12.0: 27242604
ECLASS-13.0: 27242604
ETIMETIM 9.0: EC001599
UNSPSCUNSPSC 21.0: 32151600
Descrizione
Axioline F XC, Digital output module, Digital outputs: 16, 24 V DC, 500 mA, connection method: 3-wire, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00785.pdf

Approvals_01195.pdf

Approvals_01203.pdf

Approvals_01209.pdf

Approvals_01303.pdf

Approvals_01469.pdf

Approvals_01470.pdf

Approvals_01680.pdf

Approvals_01758.pdf

Approvals_01816.pdf

Approvals_01836.pdf

Approvals_01935.pdf

Approvals_01955.pdf

Data_sheet_03256.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_01447.pdf

Manufacturer_declaration_02215.pdf

Manufacturer_declaration_05479.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_14549.pdf

Package_slip_00733.pdf

Package_slip_00734.pdf

Product_information_00033.pdf

Product_information_00285.pdf

Technical_drawing_37687.pdf

Various_00004.pdf