AXL F DI32/1 2H - Digital module

AxiolineF, Digital input module, Digital inputs: 32, 24 VDC, connection technology: 1-conductor, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Cod. Articolo: 2702052
Cod. Fornitore: 2702052
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/97375d412c926547bb2e1a41b7a47993/-S204x204-FJPG
Width: 35 mm
Height: 129.9 mm
Depth: 54 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
InterfacesAxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
ID code (hex): none
Input address area: 4 Byte
Output address area: 0 Byte
Required parameter data: 3 Byte
Required configuration data: 6 Byte
Input dataDigital
Input name: Digital inputs
Description of the input: EN 61131-2 types 1 and 3
Number of inputs: 32
Connection method: Push-in connection
Connection technology: 1-conductor
Input voltage range "0" signal: -3 VDC ... 5 VDC
Input voltage range "1" signal: 11 VDC ... 30 VDC
Nominal input voltage UIN: 24 VDC
Nominal input current at UIN: 2.4 mA
Input filter time: 3000 µs (Default)
1000 µs
< 100 µs
Protective circuit: Polarity reversal protection of the inputs; parallel diode (30V, 5s)
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (no temperature derating)
Scope of delivery: including bus base module and AxiolineF connectors
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesPotentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 120 mA (HW 00)
max. 60 mA (from HW01)
Power consumption: max. 600 mW (HW 00)
max. 300 mW (from HW01)
Potentials: Supply for digital input modules (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 50 mA
Power consumption: max. 1.2 W
Protective circuit: Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5A fuse (only for commissioning)
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
MountingMounting type: DIN rail mounting
Mounting position: any (no temperature derating)
Specifiche
ECLASSECLASS-11.0: 27242604
ECLASS-12.0: 27242604
ECLASS-13.0: 27242604
ETIMETIM 9.0: EC001599
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00785.pdf

Approvals_01195.pdf

Approvals_01199.pdf

Approvals_01203.pdf

Approvals_01209.pdf

Approvals_01303.pdf

Approvals_01759.pdf

Approvals_01836.pdf

Approvals_01893.pdf

Approvals_01935.pdf

Data_sheet_03312.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_00793.pdf

Manufacturer_declaration_02153.pdf

Manufacturer_declaration_05480.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_05563.pdf

Package_slip_00720.pdf

Product_information_00033.pdf

Product_information_00307.pdf

Technical_drawing_37748.pdf

Various_00004.pdf