PHOENIX CONTACT 2702068
PHOENIX CONTACTNon disponibile

AXL F DO4/3 AC 1F - Digital module

AxiolineF, Digital output module, Digital outputs:4 (Triac outputs with zero voltage switch), 230 VAC, 2 A, connection technology:3-conductor, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Cod. Articolo: 2702068
Cod. Fornitore: 2702068
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/4862d5b0bda14d48a6bb34e9372c151a/-S204x204-FJPG
Width: 53.6 mm
Height: 126.1 mm
Depth: 54 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
InterfacesAxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
Input address area: 0 Byte
Output address area: 1 Byte
Required parameter data: 1 Byte
Required configuration data: 6 Byte
Output dataDigital
Output name: Digital outputs
Connection method: Push-in connection
Connection technology: 3-conductor
Number of outputs: 4 (Triac outputs with zero voltage switch)
Protective circuit: External protection required; I2t-value (a half-wave): 340 A2s
Output voltage: 230 VAC
Maximum output current per module: 8 A (provide external protection)
Nominal output voltage: 230 VAC
Output voltage range: 24 VAC ... 230 VAC -20%/+15% (50/60Hz)
Load min.: 5.1 kΩ (at 230V)
Output voltage when switched off: see diagram
Nominal load, ohmic: max. 460 W (at nominal voltage)
Switching frequency: max. 100 per second (with ohmic load)
Reverse voltage resistance to short pulses: Reverse voltage proof
Behavior with overload: Output may be damaged
Signal delay: max. 10 ms (at 50 Hz)
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (observe temperature and current derating)
Scope of delivery: including bus base module and AxiolineF connectors
Electrical propertiesPotentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 120 mA
Power consumption: max. 600 mW
Potentials: Supply for digital output modules (U
Supply voltage: 230 VAC
Supply voltage range: 12 VAC ... 253 VAC (including all tolerances, including ripple, 50 ... 60 Hz)
Current draw: max. 8 A (provide external protection)
Power consumption: max. 2024 VA (of which 8VA internal losses)
Protective circuit: Surge protection; Varistor 275 V
Electrical isolation/isolation of the voltage ranges
Test voltage: I/Os / logic: 4 kV
5 kV
Test voltage: I/O/functional ground: 4 kV
5 kV
Test voltage: I/O area AC / PE: 4 kV
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30K above the ambient temperature.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.5 mm² ... 1.5 mm²
Conductor cross section flexible: 0.5 mm² ... 1.5 mm²
Conductor cross section AWG: 20 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30K above the ambient temperature.
Conductor cross section, rigid: 0.5 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.5 mm² ... 1.5 mm²
Conductor cross section AWG: 20 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C (max. 2A/channel for wall mounting on horizontal DIN rail; max. 1A/channel for any mounting position)
-25°C ... 50°C (max. 2A/channel for any mounting position)
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
MountingMounting type: DIN rail mounting
Mounting position: any (observe temperature and current derating)
Specifiche
ECLASSECLASS-11.0: 27242604
ECLASS-12.0: 27242604
ECLASS-13.0: 27242604
ETIMETIM 9.0: EC001599
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01759.pdf

Data_sheet_03314.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_00806.pdf

Manufacturer_declaration_05480.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_05563.pdf

Package_slip_00740.pdf

Product_information_00033.pdf

Product_information_00309.pdf

Technical_drawing_37750.pdf

Various_00004.pdf