PHOENIX CONTACT 2702463
PHOENIX CONTACTNon disponibile

AXL F BK PB XC - Bus coupler

AxiolineF, Bus coupler, PROFIBUS DP, D-SUB-9 female connector, Extremeconditions version, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connector
Cod. Articolo: 2702463
Cod. Fornitore: 2702463
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/aed70c619790314a9b0dbcd24cd1e6cc/-S204x204-FJPG
Width: 45 mm
Height: 126.1 mm
Depth: 74 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
InterfacesPROFIBUS DP
Number of interfaces: 1
Connection method: D-SUB-9 female connector
Transmission speed: 9.6 kbps ... 12 Mbps
AxiolineFlocal bus
Number of interfaces: 1
Connection method: Bus base module
Transmission speed: 100 Mbps
Service
Number of interfaces: 1
Connection method: Micro USB type B
Fieldbus: Local bus gateway
Max. number of local bus devices: 63 (Consider the logic current consumed by the devices)
System propertiesSystem limits
Number of supported devices: max. 63 (per station)
Number of local bus devices that can be connected: max. 63
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (observe temperature derating)
Scope of delivery: including bus base module and AxiolineF connector
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesPotentials: Communications power U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 567 mA (with 2A at UBus for the I/Os and UL = 24 V)
Power consumption: max. 13.7 W (2.0A on UBus, UL=24V)
Protective circuit: Surge protection; electronic
Reverse polarity protection; electronic
Potentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Power supply unit: max. 2 A
Electrical isolation/isolation of the voltage ranges
Test voltage: PROFIBUS interface / 24 V communications voltage (UL) feed-in: 500 VAC, 50 Hz, 1 min.
Test voltage: PROFIBUS interface / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24 V communications voltage (UL) feed-in / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: wall mounting on horizontal DIN rail)
-25°C ... 55°C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: any)
-40°C ... 70°C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
ApprovalsATEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: UL 20 ATEX 2441X
UKEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: PxCIMA22UKEX2701949X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx ULD 20.0026X
UL, USA/Canada
Identification: cULus
Certificate: E238705
UL Ex, USA / Canada
Identification: Class I, Zone 2, AEx ec IIC T4
ClassI, Division2, Groups A, B, C, D, T4
Ex ec IIC T4 Gc X
Certificate: E366272
CCC/China-Ex
Identification: Ex ec IIC T4 Gc
Certificate: , 2021122309114456
MountingMounting type: DIN rail mounting
Mounting position: any (observe temperature derating)
Specifiche
ECLASSECLASS-11.0: 27242608
ECLASS-12.0: 27242608
ECLASS-13.0: 27242608
ETIMETIM 9.0: EC001604
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00048.pdf

Approvals_01195.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01469.pdf

Approvals_01470.pdf

Approvals_01522.pdf

Approvals_01680.pdf

Approvals_01756.pdf

Approvals_01955.pdf

Data_sheet_03340.pdf

Manual_00006.pdf

Manual_00007.pdf

Manual_00142.pdf

Manufacturer_declaration_01030.pdf

Manufacturer_declaration_04193.pdf

Manufacturer_declaration_05479.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_14670.pdf

Package_slip_00699.pdf

Package_slip_00700.pdf

Package_slip_00701.pdf

Product_information_00033.pdf

Product_information_00316.pdf

Technical_drawing_37810.pdf

Various_00004.pdf