Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2702463
PHOENIX CONTACT 2702463
PHOENIX CONTACTNon disponibile

AXL F BK PB XC - Bus coupler

AxiolineF, Bus coupler, PROFIBUS DP, D-SUB-9 female connector, Extremeconditions version, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connector
Cod. Articolo: 2702463
Cod. Fornitore: 2702463
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/aed70c619790314a9b0dbcd24cd1e6cc/-S204x204-FJPG
Width: 45 mm
Height: 126.1 mm
Depth: 74 mm
Note on dimensions: The depth applies when a THÂ35-7.5 DIN rail is used (in accordance with ENÂ60715).
InterfacesPROFIBUS DP
Number of interfaces: 1
Connection method: D-SUB-9 female connector
Transmission speed: 9.6 kbps ... 12 Mbps
AxiolineÂFÂlocal bus
Number of interfaces: 1
Connection method: Bus base module
Transmission speed: 100 Mbps
Service
Number of interfaces: 1
Connection method: Micro USB type B
Fieldbus: Local bus gateway
Max. number of local bus devices: 63 (Consider the logic current consumed by the devices)
System propertiesSystem limits
Number of supported devices: max. 63 (per station)
Number of local bus devices that can be connected: max. 63
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineÂF
Mounting position: any (observe temperature derating)
Scope of delivery: including bus base module and AxiolineÂF connector
Insulation characteristics
Overvoltage category: II (IEC 60664-1, ENÂ60664-1)
Pollution degree: 2 (IEC 60664-1, ENÂ60664-1)
Electrical propertiesPotentials: Communications power U
Supply voltage: 24 VÂDC
Supply voltage range: 19.2 VÂDC ... 30 VÂDC (including all tolerances, including ripple)
Current draw: max. 567 mA (with 2ÂA at UBus for the I/Os and UL = 24 V)
Power consumption: max. 13.7 W (2.0ÂA on UBus, ULÂ=Â24ÂV)
Protective circuit: Surge protection; electronic
Reverse polarity protection; electronic
Potentials: AxiolineÂF local bus supply (U
Supply voltage: 5 VÂDC (via bus base module)
Power supply unit: max. 2 A
Electrical isolation/isolation of the voltage ranges
Test voltage: PROFIBUS interface / 24 V communications voltage (UL) feed-in: 500 VÂAC, 50 Hz, 1 min.
Test voltage: PROFIBUS interface / functional ground: 500 VÂAC, 50 Hz, 1 min.
Test voltage: 24 V communications voltage (UL) feed-in / functional ground: 500 VÂAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineÂF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the âہ“AxiolineÂF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineÂF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the âہ“AxiolineÂF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: wall mounting on horizontal DIN rail)
-25°C ... 55°C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: any)
-40°C ... 70°C (Extended, see section âہ“Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, ENÂ61140, VDEÂ0140-1)
ApprovalsATEX
Identification: ïÃ‹œ II 3 G Ex ec IIC T4 Gc
Certificate: UL 20 ATEX 2441X
UKEX
Identification: ïÃ‹œ II 3 G Ex ec IIC T4 Gc
Certificate: PxCIMA22UKEX2701949X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx ULD 20.0026X
UL, USA/Canada
Identification: cULus
Certificate: E238705
UL Ex, USA / Canada
Identification: Class I, Zone 2, AEx ec IIC T4
ClassÂI, DivisionÂ2, Groups A, B, C, D, T4
Ex ec IIC T4 Gc X
Certificate: E366272
CCCÂ/ÂChina-Ex
Identification: Ex ec IIC T4 Gc
Certificate: , 2021122309114456
MountingMounting type: DIN rail mounting
Mounting position: any (observe temperature derating)
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00048.pdf

Approvals_01195.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01469.pdf

Approvals_01470.pdf

Approvals_01522.pdf

Approvals_01680.pdf

Approvals_01756.pdf

Approvals_01955.pdf

Data_sheet_03340.pdf

Manual_00006.pdf

Manual_00007.pdf

Manual_00142.pdf

Manufacturer_declaration_01030.pdf

Manufacturer_declaration_04193.pdf

Manufacturer_declaration_05479.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_14670.pdf

Package_slip_00699.pdf

Package_slip_00700.pdf

Package_slip_00701.pdf

Product_information_00033.pdf

Product_information_00316.pdf

Technical_drawing_37810.pdf

Various_00004.pdf