Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2744652
PHOENIX CONTACTNon disponibile

PSM-CABLE-PROFIB/FC - Bus system cable

By the meter, Bus system cable, PROFIBUS (12 Mbps), shielded, PVC FR VI/PVC, violet, 2-wire (1x2xAWG22/1), color single wire: red, green, cable length: Free entry (1.0 ... 1000.0 m)
Cod. Articolo: 2744652
Cod. Fornitore: 2744652
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Data cable by the meter
Sensor type: PROFIBUS
Number of positions: 2
Shielded: yes
Electrical propertiesNominal voltage UN: 48 VAC
60 VDC
Transmission medium: Copper
InterfacesSignal type/category: PROFIBUS, 12 Mbps
Cable/lineCable length: Free entry (1.0 ... 1000.0 m)
Cable weight: 80 kg/km
UL AWM Style: 21694 (60°C / 600V)
Wiring standards/regulations: Conductor material DINEN13602 Cu-ETP-A...
Shielding material DINEN13602 Cu-ETP-A...-B
Number of positions: 2
Shielded: yes
Conductor structure: 1x2xAWG22/1
Signal speed: 0.81 c
Conductor structure signal line: 1x 0.65 mm
AWG signal line: 22
Conductor cross section: 2x 0.34 mm²
Wire diameter incl. insulation: 2.55 mm
External cable diameter: 8 mm ±0.4mm
Outer sheath, material: PVC FR VI
External sheath, color: violet
Conductor material: Bare Cu wire
Material wire insulation: PE
Single wire, color: red, green
Thickness, insulation: 0.95 mm
Thickness, outer sheath: 0.9 mm
Overall twist: 2 wires, twisted
Optical shield covering: 55 %
Insulation resistance: ≥ 16 GΩ*km
Loop resistance: ≤ 110.00 Ω/km
Cable capacity: approx. 28.5 nF/km (at 1 kHz)
≤ 1500 pF/km (asymmetrical: Conductor to ground)
Cable impedance: 150 Ω ±10% (3 ... 20 MHz)
185 Ω ±10% (31.25 ... 38.4 kHz)
270 Ω ±10% (9.6kHz)
Test voltage: 3600 VDC (3 s)
Smallest bending radius, fixed installation: ≥ 150 mm
Tensile strength: ≤ 100 N
Shield attenuation: ≤ 42 dB/km (at 16 MHz)
≤ 22 dB (at 4 МHz)
≤ 4 dB (at 38.4 kHz)
≤ 2.5 dB (at 9.6 kHz)
Flame resistance: according to IEC 60332-3-24 (Cat. C )
according to CMGFT4
Resistance to oil: Limited resistance to mineral oils and greases
according to IEC 60811-2-1, 4h at 70°C
Other resistance: Cold bending resistance according to DINVDE0473 Part811-1-4 (after 16h at -40°C)
UV resistant CL3 SUN RES
Ambient temperature (operation): -40°C ... 60°C
Specifiche
ECLASSECLASS-11.0: 27061801
ECLASS-12.0: 27061801
ECLASS-13.0: 27061801
ETIMETIM 9.0: EC003249
UNSPSCUNSPSC 21.0: 26121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Data_sheet_03436.pdf

Manufacturer_declaration_01381.pdf

Manufacturer_declaration_02425.pdf