TRIO-PS/1AC/48DC/10 - Power supply unit

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 48 V DC/10 A
Cod. Articolo: 2866501
Cod. Fornitore: 2866501
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataNominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 85 VAC ... 264 VAC (derating < 90 V AC: 2.5 % per Kelvin)
Derating: < 90 VAC (2.5%/V)
Input voltage range AC: 85 VAC ... 264 VAC (derating < 90 V AC: 2.5 % per Kelvin)
Electric strength, max.: 300 VAC
Voltage type of supply voltage: AC
Inrush current: < 15 A
Inrush current integral (I2t): < 1.4 A2s
AC frequency range: 45 Hz ... 65 Hz
Mains buffering time: > 13 ms (120VAC)
> 18 ms (230 V AC)
Current consumption: 4.6 A (120VAC)
2.4 A (230 V AC)
Nominal power consumption: 556 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): 0.96
Typical response time: < 1 s
Permissible backup fuse: B16
Recommended breaker for input protection: 16 A (Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: > 91 % (for 230 V AC and nominal values)
Output characteristic: U/I
Nominal output voltage: 48 VDC ±1%
Setting range of the output voltage (USet): 30 VDC ... 56 VDC (> 48VDC, constant capacity restricted)
Nominal output current (IN): 10 A (-25°C...55°C)
Derating: 55°C ... 70°C (2.5%/K)
Feedback voltage resistance: 60 VDC
Protection against overvoltage at the output (OVP): < 60 VDC
Max. capacitive load: unlimited
Active current limitation: Approx 11.4 A (in the event of a short-circuit)
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 50 mVPP
Output power: 480 W
Peak switching voltages nominal load: < 50 mVPP
Maximum no-load power dissipation: 8 W
Power loss nominal load max.: 49 W
Rise time: < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 9 mm
Screw thread: M2,5
Tightening torque, min: 0.4 Nm
Tightening torque max: 0.5 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.5 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.5 mm²
Conductor cross section flexible max.: 4 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 10
Stripping length: 14 mm
Screw thread: M3
SignalingTypes of signaling: LED
Operating voltage display: Green LED
Signal output
Status display: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: LED flashing
Electrical propertiesInsulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VDC (type test)
Insulation voltage input / PE: 2 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 1168000 h (40°C)
Insulation characteristics
Protection class: I (with PE connection)
Overvoltage category: III
Degree of pollution: 2
DimensionsWidth: 115 mm
Height: 130 mm
Depth: 152.5 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: horizontally 0mm, vertically 50mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: Steel sheet, zinc-plated
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): 95 % (at 25°C, non-condensing)
Shock: 15g in all directions in acc. with IEC 60068-2-27
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: EN50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: EN60950-1/VDE0805 (SELV)
EN61558-2-17
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178
Standard – Safety extra-low voltage: EN60950-1 (SELV)
EN60204 (PELV)
Standard - Safe isolation: DINVDE0100-410
ApprovalsUL approvals: UL Listed UL508
UL/C-UL Recognized UL60950-1
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN61000-4-11
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_01859.pdf

Data_sheet_03645.pdf

Manufacturer_declaration_03004.pdf

Manufacturer_declaration_04712.pdf

Manufacturer_declaration_05508.pdf

Manufacturer_declaration_15320.pdf

Package_slip_02437.pdf

Technical_drawing_39051.pdf

Various_00006.pdf