Input data | AC operation Nominal input voltage range: 100 VÃAC ... 240 VÃAC Input voltage range: 100 VÃAC ... 240 VÃAC -15Ã%Ã...Ã+10Ã% Derating IStat. Boost: < 100 VÃAC (1Ã%/V) Input voltage range AC: 85 VÃAC ... 264 VÃAC Input voltage range DC: 90 VÃDC ... 350 VÃDC Electric strength, max.: 300 VÃAC Typical national grid voltage: 120 VÃAC 230 VÃAC Voltage type of supply voltage: AC Inrush current: < 20 A Inrush current integral (I2t): < 3.2 A2s Inrush current limitation: 20 A AC frequency range: 45 Hz ... 65 Hz Frequency range DC: 0 Hz Mains buffering time: > 32 ms (120ÃVÃAC) > 32 ms (230 V AC) Current consumption: 7 A (100ÃVÃAC) 5.8 A (120ÃVÃAC) 3 A (230 V AC) 3.1 A (240ÃVÃAC) Nominal power consumption: 569 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.89 Typical response time: < 0.6 s Input fuse: 12 A (slow-blow, internal) Permissible backup fuse: B10 B16 AC: Permissible DC backup fuse: DC: Connect a suitable fuse upstream Recommended breaker for input protection: 10 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA DC operation Nominal input voltage range: 110 VÃDC ... 250 VÃDC Input voltage range: 110 VÃDC ... 250 VÃDC -18Ã%Ã...Ã+40Ã% Derating IStat. Boost: < 110 VÃDC (1Ã%/V) Current consumption: 6.3 A (110ÃVÃDC) 2.8 A (220 VÃDC)
|
Output data | Efficiency: typ. 92 % (120ÃVÃAC) typ. 92.7 % (230 V AC) Output characteristic: U/I Nominal output voltage: 24 VÃDC ñ1Ã% Setting range of the output voltage (USet): 18 VÃDC ... 29.5 VÃDC (> 24 VÃDC, constant capacity restricted) Nominal output current (IN): 20 A POWER BOOST (IBoost): 26 A (-25ðCÃ...Ã40ðC permanent, UOUT = 24ÃVÃDC ) Static Boost (IStat.Boost): 26 A Selective Fuse Breaking (ISFB): 120 A (12Ãms) Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6 Derating: 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 35 VÃDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ñ10 %) Residual ripple: < 30 mVPP (with nominal values) Short-circuit-proof: yes Output power: 480 W 624 W Maximum no-load power dissipation: 8 W Power loss nominal load max.: 40 W Rise time: < 0.1 s (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK active Output description: UOUT > 0.9 x UN: High signal Switching voltage range: 18 VÃDC ... 24 VÃDC Maximum inrush current: ââ°¤ 20 mA (short-circuit-proof) Continuous load current: ââ°¤ 20 mA Signal: DC OK floating Output description: Relay contact, UOUT > 0.9 x UN: Contact closed Maximum switching voltage: 30 VÃAC 24 VÃDC Maximum inrush current: 0.5 A 1 A Continuous load current: ââ°¤ 1 A Signal: POWER BOOST, active Output description: IOUT < IN: High signal Switching voltage range: 18 VÃDC ... 24 VÃDC Output voltage: + 24 VÃDC Maximum inrush current: 20 mA (short-circuit-proof) Continuous load current: ââ°¤ 20 mA
|
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M4 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 12 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M4 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Signal Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 10 Screw thread: M4 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm
|
Signaling | Types of signaling: LED Active switching output Relay contact Signal output: DC OK active Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED IOUT < IN: LED ON Signal output: DC OK floating Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED Signal output: POWER BOOST, active Status display: IOUT > IN: LED "BOOST" yellow
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 500 VÃDC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 900000 h (25ðC) > 520000 h (40ðC) > 235000 h (60ðC) Insulation characteristics Protection class: I Degree of pollution: 2
|
Dimensions | Width: 90 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm Alternative assembly Width: 122 mm Height: 130 mm Depth: 93 mm
|
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: PN ââ°¥50%, 5Ãmm horizontally, 15Ãmm next to active components, 50Ãmm vertically alignable: PN <50%, 0Ãmm horizontally, 40Ãmm vertically top, 20 mm vertically bottom Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Housing material: Metal Hood version: Galvanized sheet steel, free from chrome (VI) Side element version: Aluminum
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (> 2000 m, observe derating) Climatic class: 3K22 (in accordance with ENÃ60721-3-3) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min.
|
Standards and regulations | Rail applications: ENÃ50121-4 ENÃ50121-3-2 HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 61010-2-201Ã(SELV) Standard - Equipment safety: BG (design tested) Standard - Approval for medical use: IEC 60601-1, 2ÃxÃMOOP Standard ââ¬Ã¢ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMI F47-0706 Compliance Certificate Overvoltage category EN 61010-1: IIÃ(ââ°¤Ã5000Ãm) EN 62477-1: IIIÃ(ââ°¤Ã2000Ãm) ENÃ61558-2-16: IIÃ(ââ°¤Ã4000Ãm)
|
Approvals | CSA: CAN/CSA-C22.2 No.Ã60950-1-07 CSA-C22.2 No.Ã107.1-01 Shipbuilding approval: DNVÃGLÃ(EMCÃB, only with upstream filter), ABS, LR, RINA, NK, BV SIQ: BG (type approved) UL approvals: UL Listed ULÃ508 UL/C-UL Recognized ULÃ60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
|