Input data | AC operation Nominal input voltage range: 100 VÃAC ... 240 VÃAC Input voltage range: 85 VÃAC ... 264 VÃAC Derating: < 100 VÃAC (1Ã%/V) Input voltage range AC: 85 VÃAC ... 264 VÃAC Input voltage range DC: 90 VÃDC ... 300 VÃDC (UL 508: ââ°¤ 250 V DC) Electric strength, max.: 300 VÃAC Voltage type of supply voltage: AC Inrush current: < 15 A (typical) Inrush current integral (I2t): < 1.7 A2s AC frequency range: 45 Hz ... 65 Hz Frequency range DC: 0 Hz Mains buffering time: > 35 ms (120ÃVÃAC) > 35 ms (230 V AC) Current consumption: 8.8 A (120ÃVÃAC) 4.6 A (230 V AC) 9.5 A (110ÃVÃDC) 4.7 A (220 VÃDC) Nominal power consumption: 1157 VA Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester Power factor (cos phi): 0.88 Typical response time: < 0.7 s Input fuse: 20 A (slow-blow, internal) Permissible backup fuse: B16 B25 AC: Permissible DC backup fuse: DC: Connect a suitable fuse upstream Recommended breaker for input protection: 16 A ... 20 A (AC: Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA DC operation Nominal input voltage range: 120 VÃDC ... 300 VÃDC (UL 508: ââ°¤ 250 V DC) Input voltage range: 90 VÃDC ... 300 VÃDC (UL 508: ââ°¤ 250 V DC) Derating: < 120 VÃDC (0.5Ã%/V) Voltage type of supply voltage: DC
|
Output data | Efficiency: > 92 % (for 230 V AC and nominal values) Output characteristic: U/I Nominal output voltage: 24 VÃDC ñ1Ã% Setting range of the output voltage (USet): 18 VÃDC ... 29.5 VÃDC (> 24 VÃDC, constant capacity restricted) Nominal output current (IN): 40 A (-25ðCÃ...Ã60ðC, UOUT =Ã24ÃVÃDC) POWER BOOST (IBoost): 45 A (-25ðCÃ...Ã40ðC permanent, UOUT = 24ÃVÃDC ) Selective Fuse Breaking (ISFB): 215 A (12Ãms) Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / B16 / B25 / C2 / C4 / C6 / C13 Derating: 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 35 VÃDC Residual ripple: < 30 mVPP (with nominal values) Short-circuit-proof: yes Output power: 960 W Maximum no-load power dissipation: 14 W Power loss nominal load max.: 80 W Rise time: < 0.1 s (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK active Output description: UOUT > 0.9 x UN: High signal Switching voltage range: 18 VÃDC ... 24 VÃDC Output voltage: + 24 VÃDC Maximum inrush current: ââ°¤ 20 mA (short-circuit-proof) Continuous load current: ââ°¤ 20 mA Signal: DC OK floating Output description: Relay contact, UOUT > 0.9 x UN: Contact closed Maximum switching voltage: 30 VÃAC 24 VÃDC Maximum inrush current: 0.5 A 1 A Continuous load current: 1 A Signal: POWER BOOST, active Output description: IOUT < IN: High signal Switching voltage range: 18 VÃDC ... 24 VÃDC Output voltage: + 24 VÃDC Maximum inrush current: ââ°¤ 20 mA (short-circuit-proof) Continuous load current: ââ°¤ 20 mA
|
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 14 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.5 mm² Conductor cross section, rigid max.: 16 mm² Conductor cross section flexible min.: 0.5 mm² Conductor cross section flexible max.: 16 mm² Conductor cross section AWG min.: 8 Conductor cross section AWG max.: 6 Stripping length: 10 mm Screw thread: M4 Tightening torque, min: 1.2 Nm Tightening torque max: 1.5 Nm Signal Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 10 Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm
|
Signaling | Types of signaling: LED Active switching output Relay contact Signal output: DC OK active Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED IOUT < IN: LED ON Signal output: DC OK floating Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED Signal output: POWER BOOST, active Status display: IOUT > IN: LED "BOOST" yellow
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 500 VÃDC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 900000 h (25ðC) > 530000 h (40ðC) > 240000 h (60ðC) Insulation characteristics Protection class: I Degree of pollution: 2
|
Dimensions | Width: 180 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm Alternative assembly Width: 122 mm Height: 130 mm Depth: 183 mm
|
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: PN ââ°¥50%, 5Ãmm horizontally, 15Ãmm next to active components, 50Ãmm vertically alignable: PN <50%, 0Ãmm horizontally, 40Ãmm vertically top, 20 mm vertically bottom Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Housing material: Metal Hood version: Galvanized sheet steel, free from chrome (VI) Side element version: Aluminum
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: 4000 m Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): 5ÃHz ... 100ÃHz resonance search 0.7g, 90Ãmin., resonance frequency 0.7g, 90Ãmin. (in accordance with DNV GL Class A)
|
Standards and regulations | Rail applications: ENÃ50121-4 ENÃ50121-3-2 Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 61010-2-201Ã(SELV) Standard - Equipment safety: BG (design tested) Standard ââ¬Ã¢ Protection against shock currents, basic requirements for protective separation in electrical equipment: ENÃ50178 Standard ââ¬Ã¢ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Overvoltage category EN 62477-1: III
|
Approvals | CSA: CSA-C22.2 No.Ã107.1-01 Shipbuilding approval: DNVÃGLÃ(EMCÃA), ABS, LR, RINA, NK, BV UL approvals: UL Listed ULÃ508 UL/C-UL Recognized ULÃ60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) Conformity/Approvals Performance level according to ISO 13849: without
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Wireless telephone simulation Standards/regulations: ENVÃ50204 Frequency: 900 MHz 1800 MHz Field intensity: 20 V/m Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
|