Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2868716
PHOENIX CONTACTNon disponibile

STEP-PS/48AC/24DC/0.5 - Power supply unit

Primary-switched STEP POWER power supply for DIN rail and direct mounting, input: 1-phase, output: 24VDC/0.5A
Cod. Articolo: 2868716
Cod. Fornitore: 2868716
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataAC operation
Nominal input voltage range: 48 VAC
Input voltage range: 43 VAC ... 52 VAC
60 VDC ... 80 VDC
Input voltage range AC: 43 VAC ... 52 VAC
Input voltage range DC: 60 VDC ... 80 VDC
Voltage type of supply voltage: AC/DC
Inrush current: < 10 A (typical)
Inrush current integral (I2t): < 0.1 A2s
AC frequency range: 45 Hz ... 65 Hz
Frequency range DC: 0 Hz
Mains buffering time: typ. 15 ms (48VAC)
typ. 20 ms (52 V AC)
Current consumption: 0.5 A (43VAC)
0.45 A (48VAC)
Nominal power consumption: 21 VA
Power factor (cos phi): 0.7
Typical response time: < 0.5 s
Input fuse: 1.25 A (slow-blow, internal)
Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K)
Output dataEfficiency: > 81 % (for 48 VAC and nominal values)
Output characteristic: U/I
Nominal output voltage: 24 VDC ±1%
Output current Imax: 1 A
Nominal output current (IN): 0.5 A (-25°C...55°C)
0.55 A (-25°C...40°C permanent)
Derating: 55°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 35 VDC
Protection against overvoltage at the output (OVP): < 35 VDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 30 mVPP (20MHz)
Output power: 12 W
Peak switching voltages nominal load: < 20 mVPP (20MHz)
Maximum no-load power dissipation: < 0.3 W
Power loss nominal load max.: < 3.4 W
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 6.5 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 6.5 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Operating voltage display: Green LED
Signal output: LED status indicator
Status display: "DC OK" LED green
Note on status display: UOUT > 21.5 V: LED lights up
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3.75 kV AC (routine test)
3.75 kV AC (routine test)
4 kV AC (type test)
Product propertiesProduct type: Power supply
Product family: STEPPOWER
MTBF (IEC 61709, SN 29500): > 1860000 h (40°C)
Insulation characteristics
Protection class: II (in closed control cabinet)
Overvoltage category: III
Degree of pollution: 2
DimensionsWidth: 18 mm
Height: 90 mm
Depth: 61 mm
Horizontal pitch: 1 Div.
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 30 mm / 30 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: 0mm horizontally, 30mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Plastic
Polycarbonate
Foot latch material: POM (Polyoxymethylene)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (> 55°C Derating: 2.5 %/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: EN50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: IEC 62368-1(SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178
Standard – Safety extra-low voltage: IEC 62368-1 (SELV) und EN60204-1 (PELV)
Standard - Safe isolation: DINVDE0100-410
Standard - Safety of transformers: EN61558-2-16
ApprovalsUL approvals: UL/C-UL listed UL508
UL/C-UL Recognized UL60950-1
NEC Class 2 as per UL 1310
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 3 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 2 kV (Test Level 3 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 0.5 kV (Test Level 1 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Input/Output: Test Level 3
Frequency range: 150 kHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-13.0: 27040701
ECLASS-12.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00048.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Data_sheet_03686.pdf

Manufacturer_declaration_03031.pdf

Manufacturer_declaration_04738.pdf

Manufacturer_declaration_15372.pdf

Package_slip_02336.pdf

Product_information_00015.pdf

Technical_drawing_39094.pdf

Various_00006.pdf