Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2900298
PHOENIX CONTACT 2900298
PHOENIX CONTACTNon disponibile

PLC-RPT- 24DC/ 1IC/ACT - Relay Module

PLC-INTERFACE for high switch-on currents, consisting of PLC-BPT.../1 IC/ACT basic terminal block with push-in connection and plug-in miniature relay, for mounting on DIN rail NS 35/7,5, max. switch-on current up to 130A, 1 N/O contact, input voltage 24VDC
Cod. Articolo: 2900298
Cod. Fornitore: 2900298
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
NotesGeneral: Separating plate PLC-ATP must be installed for voltages larger than 250V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Product propertiesProduct type: Relay Module
Product family: PLC-INTERFACE
Application: high inrush currents
Operating mode: 100% operating factor
Mechanical service life: 3x 107 cycles
Insulation characteristics
Insulation: Safe isolation, reinforced insulation
Insulation characteristics: Standards/regulations
Insulation: Safe isolation, reinforced insulation
Overvoltage category: III
Pollution degree: 3
Electrical propertiesMaximum power dissipation for nominal condition: 0.43 W
Test voltage (Winding/contact): 4 kV AC (50Hz, 1min., winding/contact)
Standards/regulations
Rated insulation voltage: 250 VAC
Rated surge voltage: 6 kV
Input dataCoil side
Nominal input voltage UN: 24 VDC
Input voltage range: 20.2 VDC ... 33.6 VDC (20°C)
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 18 mA
Typical response time: 8 ms
Typical release time: 10 ms
Coil voltage: 24 VDC
Protective circuit: Reverse polarity protection; Polarity protection diode
Surge protection; Freewheeling diode
Operating voltage display: Yellow LED
Output dataSwitching
Contact switching type: 1 N/O contact
Type of switch contact: Single contact
Contact material: AgSnO
Maximum switching voltage: 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage: 12 V (100 mA)
Limiting continuous current: 6 A
10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged)
Maximum inrush current: 80 A (20ms)
130 A (peak, at capacitive load, 230 V AC, 24 μF)
Min. switching current: 100 mA (12V)
Interrupting rating (ohmic load) max.: 144 W (at 24 V DC)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W
85 W (for 250 V DC)
1500 VA (for 250 V AC)
Interrupting rating (ohmic load) max. bridged: 240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.)
2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.)
Switching capacity min.: 1200 mW
Switching capacity: 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
6 A (at 24 V, AC15)
6 A (at 120 V, AC15)
6 A (at 250 V, AC15)
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG: 26 ... 14
DimensionsWidth: 14 mm
Height: 80 mm
Depth: 94 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay): RT II (Relay)
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Installation location): ≥ IP54 (Installation location)
Ambient temperature (operation): -40°C ... 60°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
Shipbuilding approval
Certificate: TAE0000196
Corrosive gas test
Identification: ISA-S71.04. G3 Harsh Group
EN60068-2-60
DNV GL data
Temperature: D
Humidity: A
Vibration: B/C
EMC: B
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Electromagnetic compatibility: Conformance with EMC directive
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Specifiche
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00002.pdf

Application_note_00148.pdf

Application_note_00144.pdf

Application_note_00006.pdf

Approvals_00240.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Approvals_01883.pdf

Manufacturer_declaration_03384.pdf

Manufacturer_declaration_03385.pdf

Manufacturer_declaration_03595.pdf

Manufacturer_declaration_03598.pdf

Manufacturer_declaration_15482.pdf

Package_slip_01742.pdf

Product_information_00015.pdf

Product_information_00033.pdf

Product_information_00521.pdf

Technical_drawing_39325.pdf