Input data | AC operation Network type: Star network Nominal input voltage range: 100 VAC ... 240 VAC Input voltage range: 100 VAC ... 240 VAC -15%...+10% Switch-on voltage: > 75 VAC Shut-down voltage: < 70 VAC Electric strength, max.: 300 VAC 15 s Typical national grid voltage: 120 VAC 230 VAC Voltage type of supply voltage: AC/DC Inrush current: ⤠25 A (typical) Inrush current integral (I2t): < 0.5 A2s Inrush current limitation: typ. 25 A (after 1ms) AC frequency range: 50 Hz ... 60 Hz ±10% Mains buffering time: typ. 15 ms (120VAC) typ. 20 ms (230 V AC) Current consumption: 3.1 A (100VAC) 2.4 A (120VAC) 1.3 A (230 V AC) 1.4 A (240VAC) Nominal power consumption: 285 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.93 Typical response time: < 1 s Input fuse: 6.3 A (internal (device protection)) Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA POWER factor: > 0.9 (120VAC) > 0.9 (230 V AC) DC operation Nominal input voltage range: 110 VDC ... 250 VDC Input voltage range: 110 VDC ... 250 VDC -10%...+10% Switch-on voltage: ⥠95 VDC Shut-down voltage: < 70 VDC Voltage type of supply voltage: AC/DC Mains buffering time: > 15 ms (230 V AC) Current consumption: 2.5 A (110VDC) 1.1 A (250VDC)
|
Output data | Efficiency: > 91 % (for 230 V AC and nominal values) Output characteristic: U/I with dynamic load reserve Nominal output voltage: 24 VDC ±1% Setting range of the output voltage (USet): 24 VDC ... 28 VDC (constant capacity) Nominal output current (IN): 10 A Dynamic Boost (IDyn.Boost): 15 A (5 s) Derating: > 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ⤠35 VDC Protection against overvoltage at the output (OVP): ⤠30 VDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ±10 %) Residual ripple: < 10 mVPP (with nominal values) Short-circuit-proof: yes No-load proof: yes Output power: 240 W 360 W Maximum no-load power dissipation: < 5.1 W (230V) Power loss nominal load max.: < 25 W Rise time: ⤠12 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK Maximum switching voltage: 30 V AC/DC Continuous load current: 100 mA
|
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 8 mm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm
|
Signaling | Types of signaling: LED Floating signal contact Signal output: LED status indicator Signalization designation: DC OK Status display: LED Color: green DC OK: UOUT > 0.9 x UN
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 3 kV AC (type test) 1.5 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 1800000 h (25°C) > 1000000 h (40°C) > 480000 h (60°C) Insulation characteristics Protection class: I (in closed control cabinet) Degree of pollution: 2
|
Dimensions | Width: 42 mm Height: 130 mm Depth: 160 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm
|
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0 mm (⤠40°C) 10 mm (⤠70°C), vertically 50 mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Metal Type of housing: Aluminum (AlMg3) Hood version: Polycarbonate
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -25°C Maximum altitude: ⤠5000 m (>2000m, Derating: 10%/1000m) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ⤠95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 4g, 90 min. DNVGL CG-0339 / Class B 2 Hz - 100 Hz resonance search, 90 min. in resonance, 2 Hz - 25 Hz, ±1.6 mm amplitude, 25 Hz - 100 Hz, 4g acceleration
|
Standards and regulations | Rail applications: EN50121-4 Standard â Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV) Standard â Limitation of mains harmonic currents: EN61000-3-2 Standard - Electrical safety: IEC 62368-1(SELV) Standard â Safety extra-low voltage: IEC 62368-1 (SELV) und EN60204-1 (PELV) Standard - Safe isolation: DINVDE0100-410 Standard - Safety of transformers: EN61558-2-16 (air clearances and creepage distances only)
|
Approvals | UL approvals: UL Listed UL508 UL/C-UL Recognized UL60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) Conformity/Approvals SIL in accordance with IEC 61508: 0
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: EN61000-6-3 EN61000-6-4 EMC requirements for noise immunity: EN61000-6-1 EN61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 6 kV (Test Level 4) Discharge in air: 8 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 3 kV (Test Level 3 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 1 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Emitted interference Standards/regulations: EN61000-6-3 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
|