PHOENIX CONTACT 2903358
PHOENIX CONTACTNon disponibile

RIF-1-RSC-LDP-24DC/1X21 - Relay Module

Preassembled relay module with screw connection, consisting of: relay base, power contact relay, plug-in display/interference suppression module, and retaining bracket. Contact switching type: 1 changeover contact. Input voltage: 24 V DC
Cod. Articolo: 2903358
Cod. Fornitore: 2903358
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
NotesGeneral: FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21)
Product propertiesProduct type: Relay Module
Product family: RIFLINEcomplete
Application: Universal
Operating mode: 100% operating factor
Mechanical service life: approx. 3x 107 cycles
Insulation characteristics
Insulation: Safe isolation between input and output
Basic insulation between the changeover contacts
Insulation characteristics​
Insulation: Safe isolation between input and output
Basic insulation between the changeover contacts
Overvoltage category: III
Pollution degree: 2
Electrical propertiesService life electrical: see diagram
Maximum power dissipation for nominal condition: 0.43 W
Test voltage (Winding/contact): 4 kVrms (50Hz, 1min., winding/contact)
Rated insulation voltage: 250 VAC
Rated surge voltage: 6 kV (Input/output)
4 kV (between the changeover contacts)
Input dataCoil side
Nominal input voltage UN: 24 VDC
Input voltage range: 19.2 VDC ... 33.6 VDC (20°C)
Input voltage range in reference to UN: see diagram
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 18 mA
Typical response time: 8 ms
Typical release time: 10 ms
Coil voltage: 24 VDC
Protective circuit: Freewheeling diode
Operating voltage display: Yellow LED
Output dataSwitching
Contact switching type: 1changeover contact
Type of switch contact: Single contact
Contact material: AgNi
Maximum switching voltage: 250 V AC/DC
Minimum switching voltage: 12 V (10mA)
Limiting continuous current: 11 A (see diagram)
Maximum inrush current: 50 A (20 ms, N/O contacts)
Min. switching current: 10 mA (12V)
Interrupting rating (ohmic load) max.: 264 W (24VDC)
58 W (48VDC)
48 W (60VDC)
50 W (110VDC)
80 W (220VDC)
2750 VA (250VAC)
Utilization category CB Scheme (IEC 60947-5-1): AC15, 1.5 A/240 V (N/O contact)
AC15, 3 A/250 V (N/C contact)
DC13, 2 A/24 V (N/C contact)
DC13, 0.2 A/250 V (N/O contact)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Conductor cross section rigid: 0.5 mm² ... 4 mm²
Conductor cross-section rigid (2 conductors with same cross section): 0.5 mm² ... 2.5 mm²
Conductor cross section flexible: 0.5 mm² ... 4 mm²
0.5 mm² ... 4 mm² (Ferrule with plastic sleeve)
Conductor cross section flexible (2 conductors with same cross section): 0.5 mm² ... 2.5 mm²
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG: 20 ... 10 (solid)
20 ... 12 (flexible)
Tightening torque: 0.5 Nm ... 0.6 Nm
DimensionsWidth: 16 mm
Height: 90 mm
Depth: 75 mm
Material specificationsFlammability rating according to UL 94: V2 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Relay): RT III (Relay)
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 85°C
ApprovalsCorrosive gas test
Identification: ISA-S71.04. G3 Harsh Group
EN60068-2-60
Standards and regulationsStandards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Specifiche
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Approvals_01218.pdf

Manufacturer_declaration_01179.pdf

Manufacturer_declaration_02186.pdf

Manufacturer_declaration_15829.pdf

Package_slip_02192.pdf

Product_information_00033.pdf

Product_information_00607.pdf

Technical_drawing_39779.pdf