PHOENIX CONTACT 2904596
PHOENIX CONTACTNon disponibile

QUINT4-PS/1AC/2X15DC/2/PT - Power supply unit

Primary-switched power supply unit QUINT POWER, Push-in connection, DIN rail mounting, input:1-phase, output: 15 VDC / 2 A
Cod. Articolo: 2904596
Cod. Fornitore: 2904596
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataAC operation
Input voltage range: 100 VAC ... 240 VAC -15%...+10%
Electric strength, max.: 300 VAC 30 s
Typical national grid voltage: 120 VAC
230 VAC
Voltage type of supply voltage: AC/DC
Inrush current: < 15 A (at 25°C)
Inrush current integral (I2t): < 0.03 A2s
Inrush current limitation: < 5 A
Frequency range (fN): 50 Hz ... 60 Hz -10%...+10%
Mains buffering time: typ. 32 ms (120VAC)
typ. 32 ms (230 V AC)
Current consumption: 0.69 A (100VAC)
0.59 A (120VAC)
0.31 A (230 V AC)
0.31 A (240VAC)
Nominal power consumption: 96.3 VA
Protective circuit: Transient surge protection; Varistor
Typical response time: 300 ms
Input fuse: 3.15 A (slow-blow, internal)
Recommended breaker for input protection: 6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE: < 0.25 mA (264VAC, 60Hz)
< 0.17 mA
DC operation
Input voltage range: 110 VDC ... 250 VDC -20%...+10%
Voltage type of supply voltage: AC/DC
Inrush current integral (I2t): < 0.03 A2s
Inrush current limitation: < 5 A
Current consumption: 0.61 A (110VDC)
0.27 A (250VDC)
Output dataEfficiency: typ. 88.8 % (120VAC)
typ. 89.4 % (230 V AC)
Nominal output voltage: ± 15 VDC
Nominal output current (IN): 2 A (+)
1.4 A (-)
Static Boost (IStat.Boost): 2.5 A ((+) ≤40°C)
Dynamic Boost (IDyn.Boost): 4 A ((+) ≤60°C, 5s)
Feedback voltage resistance: ≤ 25 VDC
Protection against overvoltage at the output (OVP): ≤ 18 VDC
Control deviation: < 0.5 % (Static load change 10% ... 90%)
< 2 % (Dynamic load change 10% ... 90%, (10 Hz))
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 60 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 51 W
58.5 W
81 W
Maximum no-load power dissipation: < 1.4 W (120VAC)
< 2 W (230 V AC)
Power loss nominal load max.: < 6.6 W (120VAC)
< 6.1 W (230 V AC)
Crest factor: typ. 1.8 (120VAC)
typ. 2.2 (230 V AC)
Rise time: 50 ms (UOut=10%...90%)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal (configurable)
Digital: 0 VDC 15 VDC 24 mA
Default: 15 VDC 24 mA 15VDC for UOut >0.9xUSet
Connection dataInput
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 10 mm
Output
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 10 mm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 10 mm
SignalingTypes of signaling: LED
Signal output
POut: > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
UOut: > 0.9xUSet (LED lights up green)
< 0.9xUSet (LED flashes green)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Switching frequency: 4 kHz ... 70 kHz (Auxiliary converter stage)
80 kHz ... 190 kHz (Main converter stage)
30 kHz ... 150 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 1284000 h (25°C)
> 644000 h (40°C)
> 231000 h (60°C)
Insulation characteristics
Protection class: II
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 2 A
Temperature: 40°C
Time: 56000 h
Additional text: 120VAC
Life expectancy (electrolytic capacitors)​
Current: 2 A
Temperature: 40°C
Time: 65000 h
Additional text: 230VAC
Life expectancy (electrolytic capacitors)​​
Current: 2 A
Temperature: 25°C
Time: 168000 h
Additional text: 120VAC
Life expectancy (electrolytic capacitors)​​​
Current: 2 A
Temperature: 25°C
Time: 195000 h
Additional text: 230VAC
DimensionsWidth: 45 mm
Height: 106 mm
Depth: 90 mm
Installation dimensions
Installation distance right/left (active): 15 mm / 15 mm (POut≥50%)
Installation distance right/left (passive): 5 mm / 5 mm (POut≥50%)
Installation distance right/left (active, passive): 0 mm / 0 mm (POut≤50%)
Installation distance top/bottom (active): 30 mm / 30 mm (POut≥50%)
Installation distance top/bottom (passive): 30 mm / 30 mm (POut≥50%)
Installation distance top/bottom (active, passive): 30 mm / 30 mm (POut≤50%)
MountingMounting type: DIN rail mounting
With protective coating: No
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Plastic
Type of housing: Polycarbonate
Hood version: Polycarbonate
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K22 (in accordance with EN60721-3-3)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15Hz, ±2.5mm amplitude; 15Hz ... 100Hz: 2.3g 90Min. (in accordance with IEC 60068-2-6)
Standards and regulationsRail applications: EN50121-3-2
EN50121-4
EN50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard – Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
IEC 61010-2-201(SELV)
Standard - Safety of transformers: EN61558-2-16
Overvoltage category
EN 61010-1: II(≤5000m)
EN 62477-1: III(≤2000m)
ApprovalsSIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals: UL Listed UL61010-1
UL Listed UL61010-2-201
UL 1310 Class 2 Power Units
UL121201 & CSAC22.2No.213-17 ClassI, Division2, Groups A, B, C, D T4 (Hazardous Location)
EMC dataInterference emission: Interference emission in accordance with EN61000-6-3 (residential and commercial) and EN61000-6-4 (industrial)
Noise immunity: Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial), and EN61000-6-5 (power station equipment zone), IEC/EN61850-3 (power supply)
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant: IEC 61850-3
EN61000-6-5
Conducted noise emission: EN55016
EN61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
EN55016
EN61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN61000-3-2
EN61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: EN61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 0.5 kV (Test Level 2 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: EN61000-4-8
Frequency: 16.67 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60s
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: EN61000-4-11
Voltage: 100 VAC
Frequency: 60 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 0.5 / 1 / 30 periods
5 / 10 / 50 periods
0.5 / 1 / 5 / 50 periods
Additional text: Test Level 2
Comments: Criterion A
Criterion B
Criterion B
Pulse-shape magnetic field
Standards/regulations: EN61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations: EN61000-4-12
Input: 2 kV (symmetrical)
4 kV (asymmetrical)
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: EN61000-4-16
Test level 1: 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage: 30 V (10s)
300 V (1 s)
Test level 2: 16.67 Hz 50 Hz 60 Hz (Test Level 2)
Comments: Criterion A
Attenuated oscillating wave
Standards/regulations: EN61000-4-18
Voltage: 1 kV (symmetrical)
2.5 kV (asymmetrical)
1 kV (symmetrical)
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01297.pdf

Approvals_01330.pdf

Approvals_01335.pdf

Approvals_01628.pdf

Approvals_01629.pdf

Approvals_01630.pdf

Data_sheet_03830.pdf

Manufacturer_declaration_03303.pdf

Manufacturer_declaration_03304.pdf

Package_slip_02131.pdf

Technical_drawing_39969.pdf

Various_00006.pdf