PHOENIX CONTACT 2904955
PHOENIX CONTACTNon disponibile

PSR-MS45-1NO-1DO-24DC-SC - Safety relays

Safety relay for emergency stop and safety doors up to SIL3, Cat.4, PLe, 1 or 2-channel operation, manual, monitored start, 1 enabling current path, US=24VDC, fixed screw terminal block
Cod. Articolo: 2904955
Cod. Fornitore: 2904955
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Descrizione
Download
Caratteristiche Tecniche
Product propertiesProduct type: Safety relays
Product family: PSRmini
Application: Emergency stop
Safety door
Transponder
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3
Times
Typical response time: < 175 ms
Typical release time: < 20 ms (when controlled via A1 or S12 and S22.)
Recovery time: < 500 ms
Electrical propertiesMaximum power dissipation for nominal condition: 3 W ()
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage/insulation: Safe isolation, reinforced insulation 6kV between input circuit and enabling current path
Basic insulation 4kV between all current paths and housing
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 20.4 VDC ... 26.4 VDC
24 VDC -15% / +10%
Rated control supply current IS: typ. 42 mA
Power consumption at US: typ. 1 W
Inrush current: 4.5 A (Δt<120µs at Us)
Filter time: 1 ms (at A1 in the event of voltage dips at Us)
Protective circuit: Surge protection; Suppressor diode
Protection against polarity reversal for rated control circuit supply voltage
Input dataDigital: Sensor circuit (S12, S22)
Description of the input: safety-related sensor inputs
Input voltage range "0" signal: 0 VDC ... 5 VDC (for safe Off; at S12)
Input current range "0" signal: 0 mA ... 2 mA (for safe Off; at S12)
Inrush current: < 20 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22/Us)
> -15 mA (with Us/Ix to S22/0V)
Filter time: max. 1.5 ms (at S12, S22; test pulse width)
min. 7.5 ms (at S12, S22; test pulse rate)
Test pulse rate=5xTest pulse width
Max. permissible overall conductor resistance: 150 Ω
Current consumption: < 5 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22/Us)
> -5 mA (with Us/Ix to S22/0V)
Digital: Start circuit (S34)
Description of the input: non-safety-related
Number of inputs: 1
Input voltage range "1" signal: 20.4 VDC ... 26.4 VDC
Inrush current: < 10 mA
Max. permissible overall conductor resistance: 150 Ω
Protective circuit: Suppressor diode
Current consumption: < 10 mA
Output dataRelay: Enabling current path (13/14)
Output description: safety-related N/O contacts
Number of outputs: 1 (undelayed)
Contact switching type: 1 enabling current path
Contact material: AgSnO2
Switching voltage: min. 12 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity: min. 60 mW
Inrush current: min. 3 mA
max. 6 A
Limiting continuous current: 6 A (observe derating)
Sq. Total current: 36 A2 (observe derating)
Switching frequency: max. 0.5 Hz
Mechanical service life: 10x 106 cycles
Output fuse: 6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
Signal: M1
Output description: non-safety-related
Number of outputs: 1 (digital, PNP)
Voltage: 22 VDC (Us-2V)
Current: max. 100 mA
Maximum inrush current: 500 mA (Δt=1ms at Us)
Short-circuit protection: no
Connection dataConnection technology
pluggable: no
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 12 mm
Screw thread: M3
SignalingStatus display: 2 x green LEDs
Operating voltage display: 1 x green LED
DimensionsWidth: 6.8 mm
Height: 93.1 mm
Depth: 102.5 mm
Material specificationsHousing material: PBT
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Category: 4
Performance level (PL): e (4ADC13; 5AAC15; 8760switching cycles/year)
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 3
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -40°C ... 60°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 85°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Shock: 15g
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Certificate: CE-compliant
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: EN60947-1
MountingMounting type: DIN rail mounting
Mounting position: vertical or horizontal
Connection method: Screw connection
Specifiche
ECLASSECLASS-11.0: 27371819
ECLASS-13.0: 27371819
ECLASS-12.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Descrizione
Safety relay for emergency stop and safety doors up to SILCL 3, Cat. 4, PL e, 1 or 2-channel operation, manual, monitored start, 1 enabling current path, US = 24 V DC, fixed screw terminal block
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00165.pdf

Application_note_00183.pdf

Approvals_00379.pdf

Approvals_01216.pdf

Approvals_01217.pdf

Certification_00209.pdf

Data_sheet_03858.pdf

Manufacturer_declaration_00796.pdf

Manufacturer_declaration_01529.pdf

Manufacturer_declaration_05474.pdf

Manufacturer_declaration_15977.pdf

Package_slip_01994.pdf

Technical_drawing_40047.pdf