Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2904958
PHOENIX CONTACTNon disponibile

PSR-MS60-2NO-24DC-SC - Safety relays

Safety relay for emergency stop, safety doors, and light grids up to SIL3, Cat.4, PLe, 1 or 2-channel operation, automatic start, 2 enabling current paths (1-channel), US=24VDC, fixed screw terminal block
Cod. Articolo: 2904958
Cod. Fornitore: 2904958
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Safety relays
Product family: PSRmini
Application: Emergency stop
Safety door
Light grid
Solenoid switch
Transponder
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3
Times
Typical response time: < 175 ms
Typ. starting time with Us: < 250 ms (when controlled via A1)
Typical release time: < 20 ms (when controlled via A1 or S12 and S22.)
Recovery time: < 500 ms
Electrical propertiesMaximum power dissipation for nominal condition: 3 W ()
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage/insulation: Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24)
Basic insulation 4 kV between all current paths and housing
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 20.4 VDC ... 26.4 VDC
24 VDC -15% / +10%
Rated control supply current IS: typ. 40 mA
Power consumption at US: typ. 0.96 W
Inrush current: 4.5 A (Δt<120µs at Us)
Filter time: 1 ms (at A1 in the event of voltage dips at Us)
Protective circuit: Surge protection; Suppressor diode
Protection against polarity reversal for rated control circuit supply voltage
Input dataDigital: Sensor circuit (S12, S22)
Description of the input: safety-related sensor inputs
Input voltage range "0" signal: 0 VDC ... 5 VDC (for safe Off; at S12 and S22)
Input current range "0" signal: 0 mA ... 2 mA (for safe Off; at S12 and S22)
Inrush current: < 20 mA (with Us/Ix to S12)
< 20 mA (with Us/Ix to S22)
Filter time: max. 1.5 ms (Test pulse duration)
min. 7.5 ms (Test pulse rate)
Test pulse rate=5xTest pulse width
Max. permissible overall conductor resistance: 150 Ω
Voltage at input/start and feedback circuit: 24 VDC -15% / +10%
Current consumption: < 5 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22)
Output dataRelay: Enabling current path (13/14, 23/24)
Output description: safety-related N/O contacts (1-channel)
Number of outputs: 2 (undelayed)
Contact switching type: 2 enabling current paths
Contact material: AgSnO2
Switching voltage: min. 12 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity: min. 60 mW
Inrush current: min. 3 mA
max. 6 A
Limiting continuous current: 6 A (observe derating)
Sq. Total current: 72 A2 (observe derating)
Switching frequency: max. 0.5 Hz
Mechanical service life: 10x 106 cycles
Output fuse: 6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
Connection dataConnection technology
pluggable: no
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 12 mm
Screw thread: M3
SignalingStatus display: 2 x green LEDs
Operating voltage display: 1 x green LED
DimensionsWidth: 6.8 mm
Height: 93.1 mm
Depth: 102.5 mm
Material specificationsHousing material: PBT
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Category: 4
Performance level (PL): e (4ADC13; 5AAC15; 8760switching cycles/year)
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 3
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -40°C ... 55°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 85°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Shock: 15g
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Certificate: CE-compliant
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: EN60947-1
MountingMounting type: DIN rail mounting
Assembly instructions: See derating curve
Mounting position: vertical or horizontal
Connection method: Screw connection
Specifiche
ECLASSECLASS-11.0: 27371819
ECLASS-13.0: 27371819
ECLASS-12.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Application_note_00165.pdf

Approvals_00379.pdf

Approvals_01216.pdf

Approvals_01217.pdf

Certification_00209.pdf

Data_sheet_03860.pdf

Manufacturer_declaration_00796.pdf

Manufacturer_declaration_01529.pdf

Manufacturer_declaration_05474.pdf

Manufacturer_declaration_15980.pdf

Package_slip_01997.pdf

Technical_drawing_40050.pdf