Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

ROCKWELL AUTOMATION 100-E16EJ10
ROCKWELL AUTOMATION 100-E16EJ10
ROCKWELL AUTOMATIONDisponibile

IEC 16 A Contactor

100-E MCS-E Contactor, 16A, AC3 duty, 24-60V AC 50/60Hz / 20-60V DC Electronic Coil (low Consumption), 1 N.O. 0 N.C.
Cod. Articolo: 100-E16EJ10
Cod. Fornitore: 100-E16EJ10
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Caratteristiche Tecniche
Number of auxiliary contacts as normally open contact1
Number of auxiliary contacts as normally closed contact0
Vibration resistanceIEC 60068-2-6
Shock resistanceIEC 60068-2-27
Altitude, max3000 m of installation site
Switching frequency, max600 ops/hr, AC-1
WeightAC/DC (electronic): 0.43 kg (0.95 lbs.)
Protection classContactor main contact: IP2X
Voltage type for actuatingAC/DC
Rated control supply voltage at AC 50 Hz24 V
Rated control supply voltage at AC 60 Hz24 V
Rated control supply voltage at DC20 V
Type of electrical connection of main circuitScrew connection
Rated impulse voltage withstand (Uimp)6 kV
Operating time, closing delay40 ms
Optional overload relaysElectronic
Main current circuit resistance0.36 mΩ
Rated isolation voltage (Ui)690V per IEC
FunctionNon-reversing contactor
Energy-efficient coil, hold-in1.7VA/1.7 W @ 24-60V AC, 20-60V
Energy-efficient coil, pick-up16VA/12...16 W @ 24-60V AC, 20-60V
General purpose current (enclosed)20 A @ 600V per UL/CSA
Power dissipation1.2 W per pole at Ie, AC-1, 400V
Short time withstand (Icw)3-pole: 80 A for 30 s (40 °C)
FLA30 A @ 600V, 3-phase per UL/CSA HVAC applications
Rated operational current and power (enclosed)5 Hp @ 220-240V, 3-phase per UL/CSA
LRA180 A @ 440-480V, 3-phase AC per UL/CSA HVAC applications
Electromagnetic compatibilityIEC 60947-1 - Environment A and B (100-E09...E38 only)
Total power dissipation3.05 W at Ie, AC-3, 400V, AC/DC control (120-250V)
Operating limits, dropout(≤0.60) x Us @ DC control
Rating for switching AC motors3-poles: 9 kW @ 690V, AC-2, AC-3 (50 Hz)
Operating limits, pick-up(0.85...1.1) x Us @ 50/60 Hz
MCCB current ratingType 2 (per IEC 60947-4-1): 28 A @ 400 V, 70 kA available fault current
DIN fuses (gG) current ratingType 2 (per IEC 60947-4-1): 35 A @ 400 V, 100 kA available fault current
Rated voltage (Ue)24, 48, 110, 220, 440V DC
Coil voltage24 to 60V AC, 20 to 60V DC
Switching of lighting loadsTungsten lamps: 30 A @ 600V, 3-phase (break all lines) per UL/CSA
UL class RK5 fuses ratingType 1 Combination (per UL 60947 and CSA 22.2 No. 14): 60 A @ 600V, 5 kA available fault current
Rated operational current (Ie)3-poles: 30 A @ 40 °C, AC-1 (690V)
UL class J and CSA HRCI-J fuses ratingType 1 Combination (per UL 60947 and CSA 22.2 No. 14): 60 A @ 600V, 100 kA available fault current
UL inverse-time circuit breakerType 1 Combination (per UL 60947 and CSA 22.2 No. 14): 60 A @ 600V, 10 kA available fault current
Switching of power transformersApparent power: 9 kVA @ 208V, AC-6a, 60 Hz (n = 20)
Rated operational power (Pe)9 kW @ 690V, AC-2, AC-3 switching of 3-phase motors (50 Hz), ambient temperature 60 °C (140 °F)
Switching of DC loads3-poles in series: 30 A @ 220V (Shunt-wound motors-starting, reverse current breaking, reversing, stepping: DC-3 at 60 °C)
Optional accessoriesSide-or front-mount auxiliary contacts, Mechanical interlocks, Connecting bars
FeaturesPanel mounting or mounting on 35 mm DIN rail, AC/DC electronic coil, Made of environmentally friendly materials
Climatic withstandCategory B according to IEC 60947-1, annex Q
Ambient temperatureStorage: -60 °C...80 °C (-76 °F...176 °F)
Coil insulation classClass F per IEC 60947-4-1