ROCKWELL AUTOMATION 140G-G6C3-C25-KJ
ROCKWELL AUTOMATIONNon disponibile

Molded Case Ckt-Bkr, 125A G Frame, 65 kA at 480V, T/M - Fixed Thrm / Fixed Mgntc, 3 Poles, 25A, 80 Percent MCCB, No Bus Bar Mounting, NONE, 24V AC/DC, NONE, Aux

140G - Molded Case Circuit Breaker, G frame, 65 kA Interrupt Rating, T/M - Thermal Magnetic, 3 Poles, Rated Current 25 A, 1 No/NC AUX, 24V
Cod. Articolo: 140G-G6C3-C25-KJ
Cod. Fornitore: 140G-G6C3-C25-KJ
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Caratteristiche Tecniche
Number of poles3
Number of auxiliary contacts as change-over contact1
With integrated under voltage releaseNo
Integrated earth fault protectionNo
Complete device with protection unitYes
Rated permanent current Iu25 A
Type of control elementToggle
Rated impulse withstand voltage (Uimp)8 kV
Thermal trip current (Ir = In (fixed))25 A
Magnetic trip current (Im)500 A
Frame size125 A
Votlage for reverse-fed circuit breaker, max690V AC per IEC
Watt lossThermal magnetic type: 6 W
Insulation voltage (Ui)Rated 800V per IEC
Construction typeT/M-fixed thermal/fixed magnetic TMF
Thermal trip rating, max25 A @ ambient temperature 40 °C
Electrical life cycle8000 @ 415V AC
Interrupting rating65 kA @ 480V, 50/60 Hz per NEMA, UL, CSA
Rated ultimate short-circuit breaking capacity (Icu)IEC 60947-2: 70 kA @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
Rated service short-circuit breaking capacity (Ics)IEC 60947-2: 75% lcu @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
Motor drive integratedNo
With switched-off indicatorNo
Motor drive optionalYes
Position of connection for main current circuitFront side
Type of electrical connection of main circuitScrew connection
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalYes
Degree of protection (IP)IP40
Weight2.42 lb
Mechanical life operations25000 /h
Vibration2...13.2 Hz ±1 mm, 13.2...100 Hz ±0.7 G
ShockPeak acceleration: 150 m/s^2 peak, pulse duration 11 ms
Factory option1 NO/NC auxiliary, 24V AC/DC
Height130 mm
Device constructionBuilt-in device fixed built-in technique
Width76.2 mm
Depth70 mm
Storage temperature-40 °F
Wire temperature ratingCu 75 °C
Operational voltage (Ue)90% of voltage rating @ 3000 meter (9840 ft) altitude
Rated uninterrupted current (Iu)98% of current rating @ 3000 meter (9840 ft) altitude
Ambient temperature without derating104 °F