ROCKWELL AUTOMATION 1756-IF8IH
ROCKWELL AUTOMATION 1756-IF8IH
ROCKWELL AUTOMATIONNon disponibile

ControlLogix 8 Pt A/I HART Isolated

Isolated Analog Input Module - 8-Channel HART
Cod. Articolo: 1756-IF8IH
Cod. Fornitore: 1756-IF8IH
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Caratteristiche Tecniche
Input, currentYes
Input, voltageYes
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableYes
Output, currentNo
Output, voltageNo
Output signal configurableNo
Analogue inputs configurableYes
Analogue outputs configurableNo
Type of electric connectionScrew-/spring clamp connection
Input offset drift with temperature<=300 µA/°C
Wire typeCopper
Terminal block torque specifications1756-TBCH: 0.5 Nm (4.4 lb.in)
Inrush current400 mA @ 5V, 450 mA @ 24V
Input conversion methodSigma-Delta ADC (24-bit converter)
Module keyingElectronic, software configurable
Module error over full temperature range0.3% of range (all filters) with HART disabled
Input range0...20 mA (0...20.58 mA), 4...20 mA (3.42...20.58 mA)
Data format32-bit floating point
Wire category2 - on signal ports
Common mode noise rejection>90 dB @ 50/60 Hz (10 Hz, 15 Hz or 20 Hz filters only)
Normal mode noise rejection>90 dB @ 50 Hz and 60 Hz with 10 Hz filter, >74 dB @ 50 Hz and 60 Hz with 15 Hz filter, >33 dB @ 50 Hz and >90 dB @ 60 Hz with 20 Hz filter
Gain drift with temperature20 ppm/°C
Voltage and current ratingsBackplane: 210 mA @ 5.1V DC, 110 mA @ 24V DC, Input voltage range: 5...30V DC, Input current range: 0...20 mA, 4...20mA
Typical module HART dynamic variables update time for all channels1 s typical if all channels are HART enabled Pass through messages, handheld communications, secondary masters, communication errors, or configuration changes can significantly increase the update time.
Module scan time18...488 ms (filter dependent) for all channels - analog, minimum
InputsEight current inputs
Resolution16 to 21 Bit
Wire sizeSingle wire connection (1756-TBCH): 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm² (22...14 AWG) solid or
Calibrated accuracy0.15...1.5% of full scale, filter dependent@ 25 °C with HART disabled, 1.5% of full scale with 250 Hz filter @ 25 °C with HART enabled, 0.5% of full scale with 100 Hz filter @ 25 °C with HART enabled, 0.2% of full scale with 50 Hz or 60 Hz filter @ 25 °C
Open circuit detection time5 s (4...20 mA range only)
Suitable for safety functionsNo
Power dissipation within module4 W
Input overvoltage protection28.8V DC
Surrounding air temperature, max60 °C
North American temperature codeT5
EmissionsIEC 61000-6-4
ESD immunity6 kV contact discharges, 8 kV air discharges
EFT/B immunity±2kV at 5 kHz on signal ports
Relative humidity5...95% noncondensing
Conducted RF immunity10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Surge transient immunity±2 kV line-earth (CM) on shielded signal ports
Operating temperature0 °C
Radiated RF immunity10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature-40 °C
RTB keyingUser-defined mechanical
Vibration2 G @ 10...500 Hz
ShockOperating: 30 G, Non operating: 50 G
Slot width1
Calibration interval12 months typical
ATEX temperature codeT4
IECEx temperature codeT4
Input impedance250 Ω ±5 Ω
Isolation voltage250V (continuous), Reinforced insulation type, inputs to backplane, Basic insulation type, input to input, and inputs to ground.
Enclosure type ratingNone (open-style)