Number of analogue inputs | 2 |
Resolution of the analogue inputs | 14 Bit |
Resolution of the analogue outputs | 14 Bit |
Input, current | No |
Input, voltage | No |
Input, resistor | Yes |
Input, resistance thermometer | No |
Input, thermocouple | No |
Input signal, configurable | No |
Output, current | No |
Output, voltage | No |
Output signal configurable | No |
Analogue inputs configurable | No |
Analogue outputs configurable | No |
Type of electric connection | Screw connection |
Normal mode rejection ratio | 70 dB @ 50/60 Hz |
Accuracy | ñ1.0 ðC @ 25 ðC (77 ðF) |
Wire size | Solid: 0.14 mm2 (26 AWG)...1.5 mm2 (16 AWG) @ Rated @ 90 ðC (194 ðF) insulation maximum, Stranded: 0.14 mm2 (26 AWG)...1.0 mm2 (18 AWG) @ Rated @ 90 ðC (194 ðF) insulation maximum |
Open circuit detection time | 8 to 1212 |
Suitable for safety functions | No |
SIL according to IEC 61508 | None |
Common mode rejection ratio | 100 dB @ 50/60Hz |
RTD types supported | 100 é Platinum 385, 200 é Platinum 385, 500 é Platinum 385, 1000 é Platinum 385, 100 é Platinum 392, 200 é Platinum 392, 500 é Platinum 392, 1000 é Platinum 392, 10 é Copper 427, 120 é Nickel 672, 604 é Nickel-Iron 518 |
Surrounding air temperature, max | 65 ðC |
North American temperature code | T4 |
Power consumption | 40 mA @ 3.3V |
Emissions | CISPR 11 (IEC 61000-6-4): Class A |
ESD immunity | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges |
EFT/B immunity | IEC 61000-4-4: ñ2 kV @ 5 kHz on shielded ports |
Conducted RF immunity | IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz |
Surge transient immunity | IEC 61000-4-5: ñ2 kV line-earth(CM) on shielded ports |
Operating temperature | -20...65 ðC (-4...149 ðF): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock) |
Radiated RF immunity | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz, |
Nonoperating temperature | -40...85 ðC (-40...185 ðF), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) |
Vibration | IEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz |
Shock | IEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount: 25 g, nonoperating, Panel Mount: 35 g nonoperating |
Mounting torque | 0.2 Nm |
Terminal screw torque | 0.22...0.25 Nm (1.95...2.21 lb-in) (using a 2.5 mm (0.10 in.) flat-blade screwdriver) |
Input impedance | >5 Mé |
Explosion safety category for gas | None |
Explosion safety category for dust | None |