ROCKWELL AUTOMATION 440R-N23113
ROCKWELL AUTOMATION 440R-N23113
ROCKWELL AUTOMATION 440R-N23113
ROCKWELL AUTOMATIONNon disponibile

Safety Relay, MSR126.1T, 115VAC, Automatic/Manual, Fixed, 22.5MM Housing Width, Infinite, One 2 N.C. Input, One LC Input, 2 Safety Output, CAT 4 Rated

440R Single Function Safety Relays, Dual Channel N/A,2 N.O., , 115V AC , Fixed,Automatic/Manual Reset
Cod. Articolo: 440R-N23113
Cod. Fornitore: 440R-N23113
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Caratteristiche Tecniche
Number of outputs, safety related, undelayed, with contact2
Number of outputs, signalling function, undelayed, with contact0
Number of outputs, safety related, undelayed, semiconductors0
Number of outputs, signalling function, undelayed, semiconductors0
Number of outputs, signalling function, delayed, semiconductors0
With start inputYes
With muting functionNo
Voltage type for actuatingAC
Rated control supply voltage at DC0 V
ModelBasic device
Type of electric connectionScrew connection
Evaluation inputsOne- and two-channel
Power ON delay300 ms
Input resistance, max90 Ohm
Power consumption4 W
Terminal typeFixed
Operating voltage range97.75 V
Inductive, AC-156.0 A @ 250V AC
Inductive, DC-136 A/24V DC @ 6 ops/min
Fuses outputExternal: 6 A slow blow or 10 A quick blow
Rated thermal current (Ith)Maximum 6 A in one current path (non-switching)
Continuous safety output currentUL: B300, 5 A @ 250V AC, 24V AC, 6 A @ 24V DC, AC-15: 6 A @ 250V AC, DC-13: 3 A @ 24V DC
Wire size0.2...2.5 mm² (24...12 AWG)
Electrical life cycleOperations: 100.000 (220V AC / 4 A / 880VA cosφ = 0.35), 500.000 (220V AC / 1.7 A / 375VA cosφ = 0.6), 1.000.000 (30V DC / 2 A / 60 W), 2.000.000 (10V DC / 0.01 A / 0.1 W)
Number of outputs, signalling function, delayed, with contact0
With feedback circuitYes
Suitable for monitoring of magnetic switchesYes
Suitable for monitoring of proximity switchesYes
Suitable for monitoring of emergency-stop circuitsYes
Suitable for monitoring of optoelectronic protection equipmentYes
Suitable for monitoring of position switchesYes
Suitable for monitoring of tactile sensorsYes
Suitable for monitoring of valvesYes
Immediate safe dry No output2
Rated impulse withstand voltage2500 V
Input simultaneityInfinite
Switching current10 mA @ 10V
Resistive, DC-16.0 A @ 24V DC
Resistive, AC-16.0 A @ 250V AC
SIL according to IEC 615083
With approval according to ULYes
Stop category according to IEC 602040
Performance level according to EN ISO 13849-1Level e
Type of safety according to IEC 61496-14
With approval for TUVYes
With detachable clampsNo
Rated control supply voltage at AC 50 Hz115 V
Rated control supply voltage at AC 60 Hz115 V
Terminal protectionIP20, DIN 0470
Weight115/230V AC: 215 g (0.47 lb)
Vibration10...55 Hz, 0.35 mm
Shock10 g, 16 ms, 100 shocks
Rail mounting possibleYes
Response time15 ms
Release delayNo
Recovery time100 ms
Enclosure protectionIP40 (NEMA 1)
MTTFd375 year
DC avg99 %
T cycle8/28800 (h/s)
Mission time20 year
Hours of operation24 h
Days of operation365 Days
Performance levelup to e
Operating temperature-5 °C
Relative humidityOperating: 90%
Pollution degree2
Enclosure typeIP40 (NEMA 1), DIN 0470
PFHd2.03e-09
Categoryup to 4
Height75 mm
Width22.5 mm
Depth110 mm
MountingDIN rail: 35 mm
ResetAutomatic/manual