ROCKWELL AUTOMATION 5069-AENTR
ROCKWELL AUTOMATION 5069-AENTR
ROCKWELL AUTOMATION 5069-AENTR
ROCKWELL AUTOMATIONDisponibile

Compact 5000 EtherNet/IP Adapter

5069 Compact I/O Slim EtherNet/IP Adapter
Cod. Articolo: 5069-AENTR
Cod. Fornitore: 5069-AENTR
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Caratteristiche Tecniche
Number of HW-interfaces industrial Ethernet1
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for DeviceNetNo
Supporting protocol for other bus systemsNo
RedundancyNo
IO link masterNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for EtherNet/IPYes
Type of data transmissionModule rack extension
Thermal dissipation, max29 BTU/h
Power dissipation, max8.5 W
Enclosure type ratingNone (open-style)
Module keyingElectronic keying via programming software
RTB torque0.5...0.6 Nm (4.4...5.3 lb.in), (5069-RTB5-SCREW RTB only)
Wiring category2 - on signal ports, 1 - on power ports, 2 - on Ethernet ports
Insulation stripping length5069-RTB5-SPRING connections: 10 mm (0.39 in.), 5069-RTB5-SCREW connections: 10 mm (0.39 in.)
Wire size0.25...2.5 mm2 (22...14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.), insulation m, single wire connection only, Grounding: 2.5 mm2 (14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater,
Isolation voltage250V (continuous), basic insulation type, SA, and MOD power to backplane, 250V (continuous), basic insulation type, SA to MOD power, 250V (continuous), basic insulation type, Ethernet to backplane, type tested at 1500V AC for 60 s, 250V (continuous), doub
Supporting protocol for LONNo
Supporting protocol for ASINo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for SUCONETNo
With potential separationNo
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for PROFINET CBANo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
ATEX temp codeT4
RTB keyingNone
Width56 mm
Height138 mm
Depth105 mm
Surrounding air temperature, max60 °C
EmissionsCISPR 11/22, Class A
Vibration5 G @ 10...500 Hz
ESD immunity6 kV contact discharges, 8 kV air discharges
EFT/B immunity±3kV @ 5 kHz on power ports, ±3kV @ 5 kHz on Ethernet ports
Relative humidity5...95% noncondensing
ShockOperating: 30 G, Non operating: 50 G
Conducted RF immunity10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on power and Ethernet ports
Surge transient immunity±1kV line-line (DM) and ±2kV line-earth (CM) on power ports, ±2kV line-earth (CM) on Ethernet ports
Operating temperature0 °C
Radiated RF immunity10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz, 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature-40 °C
North American temperature codeT4
IECEx temp codeT4
MOD Power inrush1750 mA for 70 ms
MOD power220 mA @ 18...32V DC
SA power5 mA @ 0...32V DC, 2 mA @ 0...240V AC, 47...63 Hz, ATEX/IECEx, 125V AC maximum
MOD power passthrough, max9.78 A @ 18...32V DC, Maximum level of MOD Power current that the adapter can pass through to the next module in the system
SA power passthrough, max9.95 A @ 0...32V DC, 9.975 A @ 0...240V AC, 47...63 Hz, ATEX/IECEx, 125V AC maximum, Maximum level of SA power current that the adapter can pass through to the next module in the system
Recommended external overcurrent protectionMOD power: 10...12A @ 22.5...43.2 A2t, fast acting, SA power: 20 A @ 250V AC