Industrial Automation
Product properties | Product type: Safety relays Product family: PSRmini Application: Emergency stop Safety door Safety shut-off mats Light grid Times Typical response time: < 200 ms (automatic start) < 175 ms (manual, monitored start) Typ. starting time with Us: < 200 ms (with Us when controlled via A1) Response time: < 10 ms (Take the extension of the response time into consideration if you switch several devices in sequence.) Restart time: < 250 ms (Boot time) Recovery time: 250 ms (following demand of the safety function) |
Electrical properties | Maximum power dissipation for nominal condition: 3.1 W (UB=30V, IL1=IL2=2.4A) Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 50 V 50 VAC Rated surge voltage/insulation: Basic insulation 4 kV between all current paths and housing Supply Designation: A1/A2 Rated control circuit supply voltage US: 19.2 VDC ... 30 VDC 24 VDC -20%/+25% (provide external protection) Rated control supply current IS: typ. 54 mA (No load) Power consumption at US: typ. 1.3 W Inrush current: < 5 A (Ãt=200µs at Us) Filter time: 1 ms (For the logic. At A1 in the event of voltage dips at Us ) Protective circuit: Parallel protection against polarity reversal; Suppressor diode (Provide external protection, see safety notes. Fuse type: 5AFF) |
Input data | Digital: Sensor circuit (S10, S12, S22) Description of the input: safety-related sensor inputs IEC 61131-2 type3 (S10, S12) PNP (S22) Number of inputs: 3 Input voltage range "0" signal: 0 VDC ... 5 VDC (S10, S12) S22open Input voltage range "1" signal: 11 VDC ... 30 VDC (S10, S12) 0 V ... 0 V (S22) Input current range "0" signal: 0 mA ... 2 mA (S10, S12) Inrush current: < 10 mA (Typically with US at S10/S12, Ãt=500µs) > -5 mA (typ. with US at S22, Ãt=500µs) Filter time: max. 1.5 ms (Test pulse width of low test pulses) Test pulse rate=5xTest pulse width Doesnotapplyfor S22 Deactivate the switch-on pulses for safety applications. Concurrence: â Max. permissible overall conductor resistance: 150 é Protective circuit: Suppressor diode Current consumption: 4 mA (S10, S12) -4 mA (S22) Digital: Start circuit (S34, S35) Description of the input: non-safety-related Number of inputs: 2 Input voltage range "1" signal: 19.2 VDC ... 30 VDC Inrush current: < 10 mA (Typically with US, Ãt<100ms) Max. permissible overall conductor resistance: 150 é Protective circuit: Suppressor diode Current consumption: < 7 mA (Typically with US at S34) < 5 mA (Typically with US at S35) Digital: External release (S36) Description of the input: safety-related IEC 61131-2 type 3 Number of inputs: 1 Input voltage range "0" signal: 0 VDC ... 5 VDC Input voltage range "1" signal: 11 VDC ... 30 VDC Input current range "0" signal: 0 mA ... 2 mA Inrush current: < 10 mA (Ãt=500µs) Filter time: max. 1.5 ms (Test pulse width of low test pulses) Test pulse rate=5xTest pulse width Max. permissible overall conductor resistance: 150 é Protective circuit: Suppressor diode Current consumption: 7 mA |
Output data | Digital: 14, 24 Output description: Safety-related digital outputs PNP, IEC 61131-2 Type2 Number of outputs: 2 Protective circuit: Freewheeling circuit for inductive loads Output voltage: ⥠23 VDC (Us-1V) Leakage current: max. 1 mA (in the safe state) Ohmic load: min. 12 é Max. capacitive load: max. 10 µF (2.4A load) max. 4.7 µF (1A load) Max. inductive load: max. 1 H Limitation of the voltage induced on circuit interruption: max. 50 V Output current: max. 2.4 A Inrush current: max. 4.8 A (Ãt=10ms) Min. load current: 2 mA Switching frequency: 1 Hz (Resistive, inductive, capacitive) Output voltage when switched off: < 5 VDC (in the safe state) Test pulses: < 1 ms (Test pulse width of low test pulses) Signal: M1 Output description: PNP non-safety-related Number of outputs: 1 Voltage: approx. 22 VDC (Us-2V) Current: max. 100 mA Maximum inrush current: 500 mA (Ãt=1ms at Us) Protective circuit: Suppressor diode Short-circuit protection: Yes |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross-section AWG: 24 ... 16 Stripping length: 8 mm |
Signaling | Status display: 3 x green LED Operating voltage display: 1 x green LED Error indication: 1 x red LED |
Dimensions | Width: 12.5 mm Height: 116.6 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENISO13849 Category: 4 Performance level (PL): e Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 3 Safety data: ENIEC 62061 Safety Integrity Level (SIL): 3 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -40°C ... 70°C (observe derating) Ambient temperature (storage/transport): -40°C ... 70°C Maximum altitude: ⤠2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 30g Vibration (operation): 10Hz...150Hz, 5g |
Approvals | CE Identification: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: DINEN50178, EN60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: See derating curve Mounting position: vertical or horizontal Connection method: Push-in connection |
ECLASS | ECLASS-11.0: 27371819 ECLASS-12.0: 27371819 ECLASS-13.0: 27371819 |
ETIM | ETIM 9.0: EC001449 |
UNSPSC | UNSPSC 21.0: 39122200 |