Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1019121
PHOENIX CONTACTNot available

VAL-MS 1000DC-PV-ST/4 - Type 2 surge protection plug

Replacement plug for PV arrester combinations from the VAL-MS 1000DC-PV-... product range
Product Code: 1019121
Partner cod.: 1019121
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: PV II
PV T2
EN type: T2
IEC power supply system: DC
Type: Male
Product type: Replacement plug
Product family: VALVETRAB MS
Installation location: Interior
Installation location of the disconnect device: Internal
Accessibility: Accessible
SPD failure behavior: OCFM (Open-Circuit Failure Mode)
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3e02d9b64ee0a341a2e312513f1ad825/-S204x204-FJPG
Width: 17.5 mm
Height: 52.4 mm
Depth: 55.3 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6-FR
Material group: I
Housing material: PA 6.6-FR
Protective circuitStandby power consumption PC: ≤ 25 mVA
Nominal discharge current In (8/20) µs: 15 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Voltage protection level Up: ≤ 1.9 kV
Residual voltage Ures: ≤ 1.9 kV (at In)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Response time tA: ≤ 25 ns
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC: ≤ 487.5 VDC
Maximum discharge current Imax (8/20) µs: 40 kA
Response time tA: ≤ 25 ns
Insulation resistance Riso: > 5 GΩ (at 500 V DC)
Nominal discharge current In (8/20) µs: 15 kA
Continuous operating current ICPV: < 20 µA
Maximum continuous operating voltage UCPV: 585 VDC
Short-circuit current rating ISCPV: 2000 A
Residual voltage Ures: ≤ 1.9 kV (at In)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Voltage protection level Up: ≤ 1.9 kV
Standby power consumption PC: ≤ 25 mVA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 7.5g (5-500 Hz/2.5 h/XYZ)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 1170 VDC
Short-circuit current rating (SCCR): 50 kA
Voltage protection rating VPR: 3 kV
Nominal discharge current In: 10 kA
Mode of protection: (L+) - (L-)
(L+) - G
(L-) - G
Nominal voltage: 1170 VDC
Power distribution system: DCPV
SPD Type: 1CA
Standards and regulationsStandards/specifications: EN61643-31
IEC 61643-31
Note: 2019
2018
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171492
ETIMETIM 9.0: EC002496
Description
Replacement plug for PV arrester combinations from the VAL-MS 1000DC-PV-... product range
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Flyer_00001.pdf

Flyer_00002.pdf

Technical_drawing_05756.pdf