Notes | General Note: The maximum load current of a single clamping unit must not be exceeded. For power distribution applications, IEC 60364-4-43.2008; modified + corrigendum Okt. 2008 (DINVDE0100-430:2010-10) section433.2 ff must be observed! |
Product properties | Product type: Distributor terminal block Number of positions: 1 Number of connections: 13 Number of rows: 1 Potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 0.77 W |
Connection data | Service Entrance: yes Number of connections per level: 13 Nominal cross section: 2.5 mm² Load contact Stripping length: 8 mm ... 10 mm Internal cylindrical gage: A3 B3 Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 0.14 mm² ... 4 mm² Cross section AWG: 26 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section, flexible [AWG]: 26 ... 14 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.14 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.14 mm² ... 2.5 mm² Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve): 0.5 mm² Nominal current: 24 A Maximum load current: 32 A (with 4mm² conductor cross section) Maximum total current: 57 A (with 10 mm² conductor cross section) Nominal voltage: 690 V Note: The IEC 60947-7-1 standard applies for the use of mounting accessories. Nominal cross section: 2.5 mm² Line contact Stripping length: 10 mm ... 12 mm Internal cylindrical gage: A5 B4 Conductor cross section rigid: 0.5 mm² ... 10 mm² Cross section AWG: 20 ... 8 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 6 mm² Conductor cross section, flexible [AWG]: 20 ... 10 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 6 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 6 mm² Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve): 0.5 mm² ... 1.5 mm² Nominal current: 41 A (with 6 mm² conductor cross section) Maximum load current: 57 A (with 10 mm² conductor cross section) Maximum total current: The maximum load current of the individual terminal point must not be exceeded. Nominal cross section: 6 mm² Connection in acc. with standard: IEC 60998-2-2 Nominal voltage: 450 V (in accordance with IEC 60998-2-2) Load contact Connection cross sections directly pluggable Conductor cross section rigid: 0.34 mm² ... 4 mm² Conductor cross section, rigid [AWG]: 22 ... 18 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.34 mm² ... 2.5 mm² Line contact Connection cross sections directly pluggable Conductor cross section rigid: 1 mm² ... 10 mm² Conductor cross section, rigid [AWG]: 18 ... 8 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 1 mm² ... 6 mm² Flexible conductor cross section (ferrule with plastic sleeve): 1 mm² ... 6 mm² |
Dimensions | Width: 41.5 mm Height: 45.7 mm Depth: 29.2 mm Depth on NS35/7,5: 30.9 mm |
Material specifications | Color: black Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Electrical tests | Surge voltage test Result: Test passed Temperature-rise test Requirement temperature-rise test: Increase in temperature â¤45K Result: Test passed Short-time withstand current 6 mm²: 0.72 kA Short-time withstand current 10 mm²: 1.2 kA Power-frequency withstand voltage Test voltage setpoint: 1.89 kV Result: Test passed |
Mechanical properties | Mechanical data Open side panel: No |
Mechanical tests | Mechanical strength Result: Test passed Attachment on the carrier DIN rail/fixing support: NS35 Result: Test passed Note: When aligning several blocks, it is recommended to either place a DIN rail adapter underneath the connection point or a flange element between the blocks. For versions with 6 or 7 connections, it is enough to place one DIN rail adapter centrally per block and place flange elements after every other block. Depending on the application case and mechanical load, other arrangements of the mounting accessory can also be chosen. When using the DIN rail adapter PTFIX-NS35, an aligned block must not protrude by more than a half. Test for conductor damage and slackening Rotation speed: 10rpm Revolutions: 135 Conductor cross section/weight: 0.5 mm² / 0.3 kg 6 mm² / 1.4 kg 10 mm² / 2 kg Result: Test passed |
Environmental and real-life conditions | Aging Temperature cycles: 192 Result: Test passed Needle-flame test Time of exposure: 30 s Result: Test passed Oscillation/broadband noise Specification: DINEN50155 (VDE0115-200):2018-05 Spectrum: Service life test category2, bogie-mounted Frequency: f1 = 5 Hz to f2 = 250 Hz ASD level: 6.12 (m/s²)²/Hz Acceleration: 3.12g Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Specification: DINEN50155 (VDE0115-200):2018-05 Pulse shape: Half-sine Acceleration: 30g Shock duration: 18ms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) Result: Test passed Ambient conditions Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1 IEC 60998-2-2 |
Mounting | Mounting type: NS 35/7,5 NS35/15 |
ECLASS | ECLASS-11.0: 27141120 ECLASS-13.0: 27250118 |
ETIM | ETIM 9.0: EC000897 |
UNSPSC | UNSPSC 21.0: 39121400 |