Industrial Automation
Product properties | Product type: Test terminal strip Number of positions: 2 Number of connections: 8 Number of rows: 1 Potentials: 2 Insulation characteristics Overvoltage category: III |
Electrical properties | Rated surge voltage: 4 kV Maximum power dissipation for nominal condition: 1.31 W Test surge voltage: 5 kV |
Connection data | Number of connections per level: 8 Nominal cross section: 6 mm² 1 level Screw thread: No 8 UNC Tightening torque: 1.5 ... 1.8 Nm Internal cylindrical gage: A5 Connection in acc. with standard: IEC 60947-7-1 Conductor cross section flexible: 0.5 mm² ... 10 mm² Conductor cross section, flexible [AWG]: 24 ... 8 (converted acc. to IEC) 2 conductors with same cross section, solid: 0.5 mm² ... 6 mm² 2 conductors with same cross section, flexible: 0.5 mm² ... 6 mm² Maximum load current: 30 A (with 10 mm² conductor cross section) Nominal voltage: 400 V AC/DC Nominal cross section: 6 mm² Cable lug connection DIN46234:1980-03 Connection in acc. with standard: DIN46234:1980-03 DIN46237:1970-07 Cross section: 0.5 mm² ... 10 mm² Cross section range AWG: (converted acc. to IEC) Hole diameter: 4.3 mm Width: 8 mm Bolt diameter: 4.1 mm Identification color of ring cable lugs : red: 1 mm² Identification color of ring cable lugs : blue: 2.5 mm² Identification color of ring cable lugs : yellow: 6 mm² |
Material specifications | Color: green Flammability rating according to UL 94: V0 Insulating material group: I |
Mechanical properties | Mechanical data Open side panel: No |
Environmental and real-life conditions | Ambient conditions Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1 |
Mounting | Mounting type: Insertion in base strip |