Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Constant voltage source Product family: MINI Analog Pro Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
Electrical properties | Maximum temperature coefficient: < 0.01 %/K Maximum transmission error: ⤠0.1 % (of final value) Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 3 kV AC (50Hz, 60s) Insulation: Reinforced insulation according to IEC/EN61010-1 Supply Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Typical current consumption: < 38.2 mA (24V) < 79.8 mA (12V) Power consumption: < 900 mW (9.6VDC) |
Input data | Signal: Voltage Voltage input signal: 9.6 VDC ... 30 VDC Transmitter supply voltage: 15 VDC |
Output data | Signal: Voltage Max. voltage output signal: 15 VDC Short-circuit current: > 35 mA Output voltage with wire break: 15 VDC Output current: ⤠30 mA Ripple: < 20 mVPP (600é) |
Connection data | Connection method: Screw connection Stripping length: 10 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 1.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule) Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 (flexible) Tightening torque: 0.5 Nm ... 0.6 Nm |
Ex data | Ex installation (EPL): Gc Div.2 |
Signaling | Status display: Green LED (supply voltage) |
Dimensions | Width: 6.2 mm Height: 109.81 mm Depth: 119.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: BVS 20 ATEX E 014X UKCAEx(UKEX) Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIF21UKEX2902004X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx BVS 20.0010X CCC/China-Ex Identification: Ex nA IIC T4 Gc Certificate: NEPSIGYJ20.1320X UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6 Shipbuilding approval Certificate: DNV GL TAA000021E Rev. 1 DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | GBStandard Standards/regulations: GB3836.1 GB3836.8 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail. Mounting position: any |
ECLASS | ECLASS-11.0: 27040701 ECLASS-13.0: 27210192 ECLASS-12.0: 27040701 |
ETIM | ETIM 9.0: EC002498 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products