Industrial Automation
Product properties | Type: Stand-Alone Product type: Controller Product family: PLCnext Control Insulation characteristics Protection class: III (IEC 61140, EN61140, VDE0140-1) Pollution degree: 2 (when installed in a control cabinet or housing with IP54 degree of protection or higher) Display Diagnostics display: yes |
System properties | Processor: Intel® Core⢠i5-6300U 2x 2.4 GHz (Standard) Arm® Cortex®-A9, 800 MHz (CPU1) Arm® Cortex®-A8, 600 MHz (CPU2) Retentive data storage: 2 Mbyte IEC 61131 runtime system Program memory: 16 Mbyte Data storage system: 32 Mbyte PROFINET Device function: PROFINET controller, PROFINET device Update rate: min. 1 ms Conformance Class: B Number of supported devices: max. 256 Vendor ID: 00B0hex / 176dez Function Diagnostics display: yes Controller redundancy: No Safety function: yes Functionality Programming languages supported: Symbolic flowchart (SFC) Ladder diagram (LD) Function block diagram (FBD) Structured text (ST) C++ C# Java Python Simulink System requirements Engineering tool: PLCnext Engineer Eclipse Visual Studio MATLAB® Simulink® Application interface: OPCUA |
Electrical properties | Power consumption: typ. 25 W (Without fan module) max. 35 W (With fan module) Maximum power dissipation for nominal condition: max. 24 W Supply Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including ripple (3.6VPP)) Power supply connection: Screw terminal blocks, plug-in Typical current consumption: 1 A Real-time clock Realtime clock: integrated (capacitive buffering) Description realtime clock: 1.73 s/day = 20ppm at 25°C |
Connection data | COMBICON connector Conductor cross section, rigid: 0.2 mm² ... 2.5 mm² Conductor cross section, flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 |
Interfaces | Web server: yes USB Number of interfaces: 1 Connection method: USB type A, male connector Ethernet Bus system: RJ45 Number of interfaces: 4 Connection method: RJ45 jack Note on the connection method: Auto negotiation and auto crossing, auto polarity exchange Transmission speed: 10/100/1000 Mbps (LAN 1/LAN 2, half duplex or full duplex) 10/100 Mbps (LAN3.1/LAN3.2 (internally switched), half duplex or full duplex) |
Dimensions | External dimensions Width / Height / Depth: 122 mm / 182 mm / 173 mm (without fan module) 122 mm / 220 mm / 173 mm (With fan module) |
Characteristics | Safety data: ENISO13849 Category: max. 4 Performance level (PL): max. e Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): max. 3 Safety data: ENIEC 62061 Safety Integrity Level Claim Limit (SIL CL): max. 3 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (Manufacturers declaration, not evaluated by UL) Ambient temperature (operation): 0°C ... 60°C up to 2000m above mean sea level (from 40°C only with fan module) 0°C ... 55°C 2000m...3000m above mean sea level (With fan module only) 0°C ... 50°C 3000m...4000m above mean sea level (With fan module only) Ambient temperature (storage/transport): -25°C ... 70°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) Shock (operation): 20g (in accordance with EN60068-2-27/IEC 60068-2-27) Shock (storage/transport): 20g (in accordance with EN60068-2-27/IEC 60068-2-27) Vibration (operation): 1g (in accordance with EN60068-2-6/IEC 60068-2-6) Vibration (storage/transport): 1g (in accordance with EN60068-2-6/IEC 60068-2-6) Air pressure (operation): 60 kPa ... 108 kPa (up to 4000m above mean sea level) Air pressure (storage/transport): 58 kPa ... 108 kPa (up to 4500m above mean sea level) Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37: Use of the device in these ambient conditions is prohibited. |
EMC data | Conformance with EMC directives: Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Fast transients (burst)EN61000-4-4/IEC 61000-4-4 Criterion B; Supply lines: 2 kV; Signal/data lines: 2 kV Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN61000-4-5/IEC 61000-4-5 Criterion B, supply lines: 0.5kV, signal/data cables: 1kV Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Conducted interferenceEN61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V Noise emission test in accordance with EN61000-6-4/IEC 61000-6-4 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242207 ECLASS-12.0: 27242207 ECLASS-13.0: 27242207 |
ETIM | ETIM 9.0: EC000236 |