Industrial Automation
HV M8/1 NFF - High Current Connectors
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Product properties | Product type: Bolt connection terminal block Number of connections: 1 Number of rows: 1 Potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 4.73 W |
Connection data | Number of connections per level: 1 Nominal cross section: 50 mm² Stripping length: The stripping length depends on the specification provided by the cable lug manufacturer. Connection in acc. with standard: IEC 60947-7-1 NF F 61-017 Nominal current: 150 A Maximum load current: 150 A Nominal voltage: 1000 V Maximum total current: 150 A Cable lug connection DIN46234:1980-03 Connection in acc. with standard: DIN46234:1980-03 DIN46235:1983-07 DIN46237:1970-07 NFF00-363:1995-12-01 NF F00-363 Cross section: 2.5 mm² ... 50 mm² 16 mm² ... 35 mm² 2.5 mm² ... 6 mm² ... 50 mm² 10 mm² ... 50 mm² Cross section range AWG: 12 ... 2 (converted acc. to IEC) 6 ... 2 (converted acc. to IEC) 12 ... 8 (converted acc. to IEC) (converted acc. to IEC) (converted acc. to IEC) Hole diameter: 8.4 mm Width: 18 mm 20 mm 14 mm Bolt length: 30.5 mm Bolt diameter: 8 mm 6 mm Screw thread: M8 Tightening torque: 14.4 Nm Additional text: The stripping length is based on the specifications of the cable lug manufacturer. Release list on request |
Dimensions | Width: 21 mm Height: 64 mm Depth: 63.5 mm Depth on NS35/7,5: 66 mm Depth on NS35/15: 73.5 mm Bolt length: 31.5 mm |
Material specifications | Color: gray Flammability rating according to UL 94: V0 Insulating material group: I Static insulating material application in cold: -60°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Mechanical properties | Mechanical data Open side panel: No |
Environmental and real-life conditions | Oscillation/broadband noise Specification: IEC 61373:2010-05 Spectrum: Service life test category2, bogie-mounted Frequency: f1 = 5 Hz to f2 = 250 Hz ASD level: 6.12 (m/s²)²/Hz Acceleration: 30.6 m/s² Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Specification: IEC 61373:2010-05 Pulse shape: Half-sine Acceleration: 300m/s² Shock duration: 18ms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) Result: Test passed Ambient conditions Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1 NF F 61-017 |
Mounting | Mounting type: NS 35/7,5 NS35/15 |
ECLASS | ECLASS-11.0: 27141120 ECLASS-13.0: 27250101 |
ETIM | ETIM 9.0: EC000897 |
UNSPSC | UNSPSC 21.0: 39121400 |