AXL F PSAI8 I 1F - Safety module


Dimensions | Dimensional drawing: https://caas.phoenixcontact.com/caas/v1/stable/media/43924/full/b1500?format=jpg Width: 53.6 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: Housing dimensions |
System properties | Module Input address area: 18 Byte (PROFIsafe 2.6.1) Output address area: 5 Byte (PROFIsafe 2.6.1) Required parameter data: 14 Byte ((I-and F-parameters)) Required configuration data: 31 Byte |
Input data | Analog: Input name: Safe analog inputs Number of inputs: 8 (1-channel assignment) 4 (2-channel assignment) A/D converter resolution: 16 bit Connection method: Push-in connection Connection technology: 2-conductor (shielded, twisted pair) Current input signal: 4 mA ... 20 mA Input resistance current input: typ. 104 é Data formats: Standardized representation Input filter: 30 Hz Filtering: RFI filtering / passive TP 1st order Limit frequency (3 dB): 30 Hz Measured value representation: 16 bits Protective circuit: Transient protection of inputs; Suppressor diode Overload protection; No; ñ5.2 V DC, maximum, Imax = 50 mA |
Product properties | Product type: I/O component Product family: Axioline F Application: Functional safety PROFIsafe Only for connection to Phoenix Contact or Siemens controllers in PROFINET systems Type: modular Mounting position: any Operating mode: PROFIsafe 2.6.1 Data management status Article revision: 02 Insulation characteristics Overvoltage category: II (IEC 60664-1) Pollution degree: 2 (EN 60664-1) |
Electrical properties | Potentials: Axioline F local bus supply (U Supply voltage: 5 V DC (via bus base module) Current draw: max. 110 mA (at UBus 5 V DC) typ. 105 mA (at UBus 5 V DC) Potentials: I/O supply (U Supply voltage: 24 V DC (Power connector) Supply voltage range: 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current draw: max. 31 mA typ. 25.5 mA (Power supply from UA with 30 V DC) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection (parallel) Undervoltage detection; at 17 V Surge voltage detection; No |
Connection data | Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -35 °C ... 60 °C Degree of protection: IP20 Degree of protection at installation location: min. IP54 Note: Recommendation Do not use the AXL F PSAI8 I 1F in an atmosphere that contains corrosive gas. Air pressure (operation): 70 kPa ... 108 kPa Air pressure (storage/transport): 66 kPa ... 108 kPa Ambient temperature (storage/transport): -40 °C ... 85 °C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN 61140, VDE 0140-1) Air clearances and creepage distances Air clearances and creepage distances: IEC 60664-1 |