Industrial Automation
Input data | AC operation Supply system configuration: Star network (TN, TT, IT (PE)) Nominal input voltage range: 100 VAC ... 240 VAC Input voltage range: 100 VAC ... 240 VAC ±10% Switch-on voltage: > 75 VAC Shut-down voltage: < 70 VAC Electric strength, max.: ⤠300 VAC 15 s Typical national grid voltage: 120 VAC 230 VAC Voltage type of supply voltage: AC/DC Inrush current: ⤠25 A (typical) Inrush current integral (I2t): < 0.5 A2s Inrush current limitation: typ. 25 A (after 1ms) AC frequency range: 50 Hz ... 60 Hz ±10% Frequency range (fN): 50 Hz ... 60 Hz ±10% Mains buffering time: > 15 ms (120VAC) > 15 ms (230 V AC) Current consumption: 2.2 A (100VAC) 0.9 A (240VAC) Nominal power consumption: 285 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): > 0.93 Switch-on time: < 1 s Input fuse: 6.3 A (internal (device protection)) Recommended breaker for input protection: 6 A ... 16 A (US/CAN: branch circuit protection <20A) (Characteristic B, C, D, K or comparable) Discharge current to PE: < 3.5 mA DC operation Nominal input voltage range: 110 VDC ... 250 VDC Input voltage range: 110 VDC ... 250 VDC ±10% Switch-on voltage: ⥠95 VDC Shut-down voltage: < 95 VDC Voltage type of supply voltage: AC/DC Mains buffering time: > 15 ms (230 V AC) Current consumption: 1.9 A (110VDC) 0.8 A (250VDC) |
Output data | Efficiency: typ. 91 % (120VAC) typ. 93 % (230 V AC) Nominal output voltage: 24 VDC ±1% Nominal output current (IN): 8 A Dynamic Boost (IDyn.Boost): 12 A (5 s) Derating: > 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ⤠35 VDC Protection against overvoltage at the output (OVP): ⤠30 VDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ±10 %) Residual ripple: ⤠10 mVPP Short-circuit-proof: yes No-load proof: yes Output power: 192 W 288 W Maximum no-load power dissipation: < 8 W (120VAC) < 5 W (230 V AC) Power loss nominal load max.: < 18 W (120VAC) < 14 W (230 V AC) Rise time: ⤠12 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK Maximum switching voltage: 30 V AC/DC Continuous load current: 100 mA Signal relay 13/14 Default: closed Digital: 30 VAC 30 VDC 100 mA |
Connection data | Input Connection method: 7/8â³ circular connector Type of locking: Screw locking mechanism Number of positions: 3 Output Connection method: 7/8â³ circular connector Type of locking: Screw locking mechanism Number of positions: 4 |
Signaling | Types of signaling: LED Floating signal contact Status display: 2 x green LEDs Signal output: LED status indicator Signalization designation: AC OK Status display: LED Color: green AC OK: ACIn>0.55xACN (ACN=90VAC) Signal output: LED status indicatorâ Signalization designation: DC OK Status display: LED Color: green DC OK: UOUT > 0.9 x UN (UN = 24VDC) |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 3 kV AC (type test) 1.5 kV AC (routine test) |
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 1200000 h (25°C) > 700000 h (40°C) > 300000 h (60°C) Insulation characteristics Protection class: I Degree of pollution: 3 |
Dimensions | Item dimensions Width: 136 mm Height: 240 mm Depth: 53 mm Drill hole Diameter: 5.6 mm |
Mounting | Mounting type: Wall mounting Assembly instructions: Alignable: 20mm horizontally, 50mm vertically above, 100mm vertically below With protective coating: No |
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Metal Type of housing: Aluminum (AlMg3) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP67 Ambient temperature (operation): -25°C ... 70°C (Derating>60°C: 2.5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ⤠4000 m (>2000m, Derating: 10%/1000m) Climatic class: 4K26 (EN60721-3-4) Max. permissible relative humidity (operation): ⤠100 % (at 25°C, non-condensing) Permissible humidity (operation): ⤠100 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 4g, 90 min. |
Standards and regulations | Overvoltage category EN 61010-1: III(â¤2000m) II(â¤4000m) Electrical safety Standard designation: Electrical safety Standards/specifications: IEC 61010-1 Protective extra-low voltage Standard designation: Protective extra-low voltage Standards/specifications: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Safe isolation Standard designation: Safe isolation Standards/specifications: IEC 61558-2-16 Low-voltage power supplies, DC output Standard designation: Low-voltage power supplies, DC output Standards/specifications: EN61204-3 Safety requirements for electrical equipment for measurement, control, and laboratory use Standard designation: Safety requirements for electrical equipment for measurement, control, and laboratory use Standards/specifications: IEC 61010-1 Limit values for harmonic currents Standard designation: Limit values for harmonic currents Standards/specifications: EN61000-3-2 Degrees of protection provided by enclosures (IP code) Standard designation: Degrees of protection provided by enclosures (IP code) Standards/specifications: EN/IEC 60529 |
Approvals | UL Identification: UL/C-UL Listed UL61010-1 ULâ Identification: UL/C-UL Listed UL61010-2-201 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Interference emission in accordance with EN61000-6-3 (residential and commercial) and EN61000-6-4 (industrial) Noise immunity: Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial) Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: EN55016 EN61000-6-3 (Class B) Noise emission: EN 55011 (EN 55022) EN55016 EN61000-6-3 (Class B) Harmonic currents Standards/regulations: EN61000-3-2 EN61000-3-2 (Class A) Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 6 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 3 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: EN61000-4-11 Voltage: 230 VAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 25 periods 10 periods 1 period Comments: Criterion A Emitted interference Standards/regulations: EN61000-6-3 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |