Industrial Automation
BLT-T2-1S-305-UT - Type 2 surge arrester
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Product properties | IEC test classification: II / III EN type: T2 / T3 IEC power supply system: TN-S TT Distance between live and grounded parts: 3 mm Product type: Surge arrester Installation location of the disconnect device: Internal Accessibility: Accessible SPD failure behavior: OCM Surge protection fault message: optical Insulation characteristics Protection class: I Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Nominal voltage UN: 100 VAC ... 230 VAC (TN-S) 100 VAC ... 230 VAC (TT) Dielectric strength: < 2.2 kV (1min) |
Connection data | Connection method: Screw terminal blocks Screw thread: M3 Tightening torque: 0.6 Nm Stripping length: 8 mm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/a2fcb1c895e79649b1bcc31ef43b0d84/-S204x204-FJPG Width: 36.5 mm Height: 56 mm Depth: 34 mm |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6 Material group: I Housing material: PA 6.6 |
Protective circuit | Mode of protection: L-N L-PE N-PE Nominal voltage UN: 100 VAC ... 230 VAC (TN-S) 100 VAC ... 230 VAC (TT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous operating voltage UC (L-N): 305 VAC Maximum continuous operating voltage UC (L-PE): 265 VAC Maximum continuous operating voltage UC (N-PE): 265 VAC Rated load current IL: 16 A Residual current IPE: ⤠5 µA Nominal discharge current In (8/20) µs (L-N): 5 kA Nominal discharge current In (8/20) µs (L-PE): 5 kA Nominal discharge current In (8/20) µs (N-PE): 10 kA Maximum discharge current Imax (8/20) µs (L-N): 10 kA Maximum discharge current Imax (8/20) µs (L-PE): 10 kA Maximum discharge current Imax (8/20) µs (N-PE): 20 kA Combination wave UOC (L-N): 10 kV Combination wave UOC (L-PE): 10 kV Combination wave UOC (N-PE): 20 kV Total discharge current Itotal (8/20)µs: 20 kA Follow current interrupt rating Ifi (N-PE): 100 A () Short-circuit current rating ISCCR: 10 kA (6A gG backup fuse) 3 kA (16A MCB B/C backup fuse) Voltage protection level Up (L-N): ⤠1.3 kV Voltage protection level Up (L-PE): ⤠1.5 kV Voltage protection level Up (N-PE): ⤠1.5 kV TOV behavior at UT (L-N): 336 VAC (5s / withstand mode) 440 VAC (120min / safe failure mode) TOV behavior at UT (L-PE): 440 VAC (5s / withstand mode) 440 VAC (120min / safe failure mode) TOV behavior at UT (N-PE): 1200 VAC (200ms / safe failure mode) Response time tA (L-N): ⤠25 ns Response time tA (L-PE): ⤠100 ns Response time tA (N-PE): ⤠100 ns Max. backup fuse with V-type through wiring: 16 A (MCB B/C) Max. backup fuse with branch wiring: 16 A (MCB B/C) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
Standards and regulations | Standards/specifications: IEC 61643-11 Note: 2011 EN 61643-11 Standards/specifications: EN61643-11 Note: 2012 |
Mounting | Mounting type: 4 mm screw Mounting position: Internal |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 8.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |